12.5
Application and function of the
analogue inputs AI1 and AI2
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Communication interfaces: Setting and function
Main pump
States
EXT.
Behaviour
OFF
of the
pump mo-
tor
4
Not act-
On
ive
Table 27: Single mode
Combined mode
The control input DI1 is equipped in the factory with a converter bridge and the func-
tion "EXT. OFF" is active. The control input of the main pump switches both twin-
head pump partners off. The control input of the partner pump only switches the
partner pump off. If the main pump fails or the twin-head pump connection is discon-
nected, the control input of the partner pump is evaluated.
Main pump
States
EXT.
Behaviour
OFF
of the
pump mo-
tor
1
Active
Off
2
Not act-
On
ive
3
Active
Off
4
Not act-
On
ive
Table 28: Combined mode
NOTICE
In regular operation, it is preferable to switch the pump on or off via the DI input
with EXT. OFF instead of via the mains voltage!
NOTICE
The 24 V DC power supply is only available when the analogue input AI1 or AI2 has
been configured to a type of use and a signal type or when the digital input DI1 has
been configured.
Analogue inputs can be used for setpoint input or actual value input. The assignment of
the target and actual value specifications depends on the selected control mode.
Analogue input AI1 is used as actual value input (sensor value). Analogue input AI2 is
used as setpoint input.
Set control mode
Δp-v
Partner pump
Display
EXT.
text for
OFF
active in-
fluences
OK; normal
Not act-
operation
ive
Partner pump
Display
EXT.
text for
OFF
active in-
fluences
OFF
Active
Override
OFF (DI1)
OK; normal
Active
operation
OFF
Not act-
Override
ive
OFF (DI1)
OK; normal
Not act-
operation
ive
Function of analogue in-
put AI1
Configured as actual value
input
ƒ
Type of use: Differen-
tial pressure sensor
Configurable:
ƒ
Signal type
ƒ
Sensor measurement
range
ƒ
Sensor position
en
Behaviour
Display
of the
text for
pump mo-
active in-
tor
fluences
On
OK; normal
operation
Behaviour
Display
of the
text for
pump mo-
active in-
tor
fluences
Off
OFF
Override
OFF (DI1)
Off
OFF
Override
OFF (DI1)
Off
OFF
Override
OFF (DI1)
On
OK; normal
operation
Function of analogue in-
put AI2
Not configured
Can be used as a setpoint
input
173