9

Commissioning

9.1

Filling and venting

Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Commissioning
NOTICE
Explanations on commissioning as well as application, function and configuration of
the CIF module on the pump are described in the installation and operating instruc-
tions for the CIF modules.
ƒ
Electrical work: Electrical work must be performed by a qualified electrician.
ƒ
Installation/dismantling work: The installation/dismantling must be carried out by a
qualified technician who is trained in the use of the necessary tools and fixation
materials.
ƒ
The product must be operated by persons who are instructed on how the complete
system functions.
DANGER
Risk of fatal injury due to lack of protective devices!
Due to missing protective devices of the electronic module or in the range of the
coupling/motor, electric shock or contact with rotating parts can lead to life-threat-
ening injuries.
• Before commissioning, safety devices such as electronic module covers or coup-
ling covers that were removed must be reinstalled!
• An authorised technician must check the functionality of the safety devices on
the pump and motor prior to commissioning!
• Never connect the pump without the electronic module!
WARNING
Danger of injury due to fluid shooting out and components coming loose!
Not installing the pump/system correctly can lead to serious injuries during commis-
sioning!
• Carry out all work carefully!
• Keep a safe distance during commissioning!
• Always wear protective clothing, protective gloves and protective goggles when
working.
CAUTION
Dry running will destroy the mechanical seal! It may cause leakage.
• Ensure that a dry run of the pump is not possible.
WARNING
There is a risk of burns or freezing upon coming into contact with the
pump/system.
Depending on the pump and system operating conditions (fluid temperature), the
entire pump can become very hot or very cold.
• Keep a safe distance during operation!
• Allow the system and pump to cool to room temperature!
• Always wear protective clothing, protective gloves and protective goggles when
working.