Pump cycling
Time-based pump
cycling: ON/OFF
Time-based pump
cycling: Interval
Manual pump cycling
Fig. 56: Pump cycling menu
Dual pump
management
Twin-head pump function
Pump cycling
Pump housing type
Fig. 57: Dual pump management menu
164
Double pump operation
"Pump cycling" menu
If a twin-head pump connection has been established, the function can be switched on
and off and the time interval of the pump cycling can be set in the "Pump cycling"
menu. Time interval: between 1 h and 36 h, factory setting: 24 h.
Universal
Display text
1.4.4
Pump cycling
1.4.4.1
Time-based pump
cycling: ON/OFF
1.4.4.2
Time-based pump
cycling: Interval
1.4.4.3
Manual pump
cycling
Confirm
Confirm
Cancel
Cancel
An immediate pump cycling can be triggered via the menu item "manual pump cycling".
Manual pump cycling can always be carried out regardless of the configuration of the
time-based pump cycling function.
Menu "Disconnect twin-head pump"
When a twin-head pump function is established, it can also be separated. To do this,
select the following:
Universal
Display text
1.0
Settings
1.4
Dual pump management
1.4.2
Disconnecting twin-head pump
Confirm (Pump might
Confirm
reset!)
(Pump might reset!)
NOTICE
Disconnecting the twin-head pump function fundamentally changes various para-
meters of the pump. The pump is then started automatically.
"Pump housing type" menu
The selection at which hydraulic position a motor head is mounted is made independ-
ently of a twin-head pump connection.
The following selection is available in the "Pump housing type" menu:
ƒ
Single pump hydraulics
ƒ
Twin-head pump hydraulics I (left in flow direction)
ƒ
Twin-head pump hydraulics II (right in flow direction)
WILO SE 2022-05