Wilo Yonos GIGA2.0-I Installation And Operating Instructions Manual page 169

Table of Contents

Advertisement

Available languages

Available languages

Twin-head pump
SSM relay function
System mode (SSM)
Single pump mode (ESM)
Fig. 63: Twin-head pump SSM relay function
menu
12.2.2
SBM application and function
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Communication interfaces: Setting and function
Universal
Display text
1.3.1
Relay output (SSM/SBM)
1
1.3.1.2
SSM relay function
1.3.1.2 / 1
Error present
1.3.1.2 / 2
Error or warning present
1
Depending on the usage selection, SBM or SSM opens as a submenu.
Possible settings:
Selection option
Only fault (factory setting)
Faults and warnings
Table 22: Function SSM relay
SSM/ESM (collective fault signal/individual fault signal) in twin-head pump opera-
tion
ƒ
SSM: The SSM function must preferably be connected to the main pump.
The SSM contact can be configured as follows: the contact reacts either only in the
event of a fault or in the event of a fault and a warning.
Factory setting: SSM only reacts in the event of a fault.
Alternatively or additionally, the SSM function can also be activated on the standby
pump. Both contacts work in parallel.
ƒ
ESM: The ESM function of the twin-head pump can be configured on each twin-
head pump head as follows:
The ESM function on the SSM contact only signals faults of the respective pump
(individual fault signal). In order to detect all faults of the two pumps, the contacts
must be assigned in both drives.
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.1
Relay output (SSM/SBM)
2
1.3.1.4
Twin-head pump
SSM relay function
SSM
System mode (SSM)
ESM
Single pump mode (ESM)
2
These submenus appear only when the twin-head pump is connected and depending
on the selection of SSM or SBM.
The contact of the collective run signal (SBM, potential-free changeover contact) can
be connected to a building automation system. The SBM contact signals the operating
status of the pump.
ƒ
The SBM contact can be assigned to any of the two pumps. The following config-
uration is possible:
The contact is activated when the motor is in operation, power supply is present
(network-ready) or no fault is present (ready for operation).
Factory setting: ready for operation. Both contacts signal the operating status of
the twin-head pump in parallel (collective run signal).
Depending on the configuration, the contact is set to NO or NC.
To do this, select the following in the menu:
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.1
Relay output (SSM/SBM)
1
Function SSM relay
SSM relay connects only in case of fault. Fault
means: The pump is not running.
SSM relay connects only in case of fault or a warn-
ing.
2
en
169