60Hz Single Phase Front-Mounted Equipment Receptacles And Circuit Breakers With Ground Fault Circuit Interrupters (Gfci) - Standard Receptacles - Vanguard CPW 125-4-S Series Operation And Maintenance Manual

Weld-deck welding package
Table of Contents

Advertisement

60Hz Single Phase Front-Mounted Equipment Receptacles and Circuit Breakers with Ground
Fault Circuit Interrupters (GFCI) — Standard Receptacles
RC 1
RC 2
Figure 34: 60 Hz Single Phase Front-Mounted Equipment Receptacles and Circuit Breakers with Ground Fault Circuit
Interrupters (GFCI)
Each of the 60Hz single phase equipment circuit breakers energizes one of the dedicated 60Hz single phase receptacles on
the front of the control/distribution center, refer to the Genset Frequency Configuration—60Hz Mode in the Maintenance
and Lubrication section of this manual for 60Hz configuration set-up instructions. Each circuit breaker will independently
trip if an over current condition arises in its dedicated circuit.
Each of the 60Hz single phase equipment circuit breakers incorporates a Ground Fault Circuit Interrupter (GFCI). A GFCI is
a device whose function is to interrupt the electric circuit to a load when a fault current to ground exceeds a predetermined
value, that is less than that required to operate the over current protective device of the supply circuit.
GFCIs are designed to shut off electric power when the current going into the electric equipment does not equal the amount
of current returning to the GFCI. A GFCI interrupts the unbalanced current flow in a fraction of a second, to prevent
electrocution. GFCIs only protect against unbalanced current flow type faults, some current must be returned through
another path for the GFCI to trip. GFCIs do not protect against line to line or line to neutral contact hazards such as result
037-08OP-002D-01
60Hz, Single
Phase circuit
breakers with
GFCIs, CB17
- CB 23
037-05-63-311B
RC 6
RC 3
RC 4
RC 5
037-05-63-315A
S/N CB50600021 – UP (Weld-deck)
RC 7
CB16
CB9
CB8
CB7
CB6
CB5
CB4
CB3
037-05-63-314A
50