Drive Specifications - YASKAWA GA800 Maintenance & Troubleshooting

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

7.6 Drive Specifications

7.6

Drive Specifications

Note:
• To get the OLV, CLV, and AOLV specifications, do Rotational Auto-Tuning.
• To get the longest product life, install the drive in an environment that meets the necessary specifications.
Item
• V/f Control
• V/f Control with Encoder
• Open Loop Vector
• Closed Loop Vector
• Advanced Open Loop Vector
Control Methods
• PM Open Loop Vector
• PM Advanced Open Loop Vector
• PM Closed Loop Vector
• EZ Vector Control
• Models 2004 to 2138, 4002 to 4103, and T103
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
• Models 2169 to 2415, 4140 to 4414, and T140 to T414
HD: 5 kHz without derating the drive capacity.
Carrier Frequency
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 10 kHz maximum.
• Models 4477 to 4720, and T477 to T720
HD: 2 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 5 kHz maximum.
• 200 V Class: Three-phase 200 V to 240 V
• 400 V Class: Three-phase 380 V to 480 V
Maximum Output
Voltage
Note:
The maximum output voltage is proportional to the input voltage.
• AOLV and EZOLV: 0.01 Hz to 120 Hz
Frequency Control
• CL-V/f, CLV, AOLV/PM, and CLV/PM: 0.01 Hz to 400 Hz
Range
• V/f, OLV, and OLV/PM: 0.01 Hz to 590 Hz
Frequency Accuracy
Digital inputs: ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
(Temperature
Analog inputs: In ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Fluctuation)
Digital inputs: 0.01 Hz
Frequency Setting
Resolution
Analog inputs: 1/2048 of the maximum output frequency (11-bit signed)
Output Frequency
0.001 Hz
Resolution
Main speed frequency reference: -10 Vdc to +10 Vdc (20 kΩ), 0 Vdc to 10 Vdc (20 kΩ), 4 mA to 20 mA (250 Ω), 0 mA to 20 mA (250 Ω)
Frequency Setting
Signal
Main speed reference: Pulse train input (maximum 32 kHz)
• V/f: 150%/3 Hz
• CL-V/f: 150%/3 Hz
• OLV: 200%/0.3 Hz
• CLV: 200%/0 min
• AOLV: 200%/0.3 Hz
• OLV/PM: 100%/5% speed
• AOLV/PM: 200%/0 min
• CLV/PM: 200%/0 min
• EZOLV: 100%/1% speed
Starting Torque
Note:
• Correctly select the drive and motor capacity for this starting torque in these control methods:
–OLV
–CLV
–AOLV
–AOLV/PM
–CLV/PM
• Set n8-57 = 1 [HFI Overlap Selection = Enabled] for this starting torque in AOLV/PM. When you use a non-Yaskawa PM motor, do Rotational Auto-
Tuning.
518
Table 7.11 Control Characteristics
-1
(r/min)
-1
(r/min)
-1
(r/min)
Specification
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents