YASKAWA GA800 Maintenance & Troubleshooting page 210

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

3.10 H: Terminal Functions
Setting Value
Function
10
Alarm
11
Fault Reset Command
Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selected
210
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a minor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or the
communication option.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the terminal as the timer output. Use this setting with the timer input set in H1-xx = 18 [MFDI Function Selection = Timer
Function].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width
(+/-)].
Note:
• The detection function operates in the two motor rotation directions.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-04 [Speed
Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.
Note:
• The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ± L4-04.
OFF : The output frequency is not in the range of "L4-03 ± L4-04" or the range of frequency reference ± L4-04.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency > "L4-03 [Speed Agree Detection Level(+/-)] + L4-04 [Speed Agree Detection
Width(+/-)]". After the terminal deactivates, the terminal stays deactivated until the output frequency is at the value of L4-03.
Note:
• The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency < L4-03, or the output frequency ≤ "L4-03 + L4-04"
OFF : The output frequency > "L4-03 + L4-04"
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency > L4-03 [Speed Agree Detection Level(+/-)]. After the terminal activates, the
terminal stays activated until the output frequency is at the value of "L4-03 - L4-04".
Note:
• The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency > L4-03
OFF : The output frequency < "L4-03 - L4-04", or the output frequency ≤ L4-03
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-02 for longer than the time
set in L6-03 [Torque Detection Time 1].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer than the time set
in L6-06 [Torque Detection Time 2].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer than the time
set in L6-06 [Torque Detection Time 2].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when you select motor 2.
ON : Motor 2 Selected
OFF : Motor 1 Selected
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting