YASKAWA GA800 Maintenance & Troubleshooting page 125

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Code
Name
Code
Name
oPE05
Run Cmd/Freq Ref Source Sel Err
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Causes
These commands are set in Digital Inputs (H1-xx, F3-
10 to F3-25, and H7-01 to H7-04) at the same time:
• Setting values 61 [Speed Search from Fmax] and
62 [Speed Search from Fref]
• Setting values 65, 66, 7A, 7B [KEB Ride-Thru 1 or
2 Activate] and 68 [High Slip Braking (HSB)
Activate]
• Setting values 16 [Motor 2 Selection] and 1A
[Accel/Decel Time Selection 2]
• Setting values 65, 66 [KEB Ride-Thru 1 Activate]
and 7A, 7B [KEB Ride-Thru 2 Activate]
• Setting values 40, 41 [Forward RUN (2-Wire),
Reverse RUN (2-Wire)] and 42, 43 [Run
Command (2-Wire Sequence 2), FWD/REV (2-
Wire Sequence 2)]
• Setting values 60 [DC Injection Braking
Command] and 6A [Drive Enable]
• Setting values 16 [Motor 2 Selection] and 75, 76
[Up 2 Command, Down 2 Command]
Settings for N.C. and N.O. input [H1-xx] for these
functions were selected at the same time:
• Setting value 15 [Fast Stop (N.O.)]
• Setting value 17 [Fast Stop (N.C.)]
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 4 [Frequency Reference Selection 2 =
Pulse Train Input]
• H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠
Frequency Reference]
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 3 [Option PCB] or b1-16 = 3 [Run
Command Selection 2 = Option PCB]
• No option card is connected to the drive.
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 1 [Analog Input]
• H3-02 ≠ 0 [Terminal A1 Function Selection ≠
Frequency Reference] or H3-10 ≠ 0 [Terminal A2
Function Selection ≠ Frequency Reference]
These parameters are set at the same time:
• H1-xx ≠ 6A [Drive Enable]
• H2-xx = 38 [Drive Enabled]
These parameters are set at the same time:
• H6-01 ≠ 3 [PG Speed Feedback (V/F Control)]
• H1-xx = 7E [Reverse Rotation Identifier]
These parameters are set at the same time:
• H1-xx = 75/76 [Up 2 /Down 2 Command]
• H3-01, H3-05, H3-09 = 1 [Terminal A1, A2, A3
Signal Level Select = -10 to +10V (Bipolar
Reference)]
These parameters are set at the same time:
• H1-xx = 62 [Speed Search from Fref]
• H5-22 = 1 [Speed Search from MODBUS =
Enabled]
These settings do not agree:
• A PG-RT3 option is connected to the drive.
• H1-xx = 16 [Motor 2 Selection] is set.
Causes
The setting to assign the Run command or frequency
reference to an option card or the pulse train input is
incorrect.
b1-01 = 3 [Frequency Reference Selection 1 =
Option PCB] is set, but there is no option card
connected to the drive.
b1-02 = 3 [Run Command Selection 1 = Option
PCB] is set, but there is no option card connected to
the drive.
2.6 Parameter Setting Errors
Possible Solutions
Remove the function settings that are not in use.
Remove one of the function settings.
Set H6-01 = 0.
Connect an input option card to the drive.
Set H3-02 = 0 or H3-10 = 0.
Correct the parameter settings.
Correct the parameter settings.
Remove one of the function settings.
Remove one of the function settings.
Correct the parameter settings.
Note:
The Motor Switch function is not available with the PG-RT3
option.
Possible Solutions
Correct the parameter settings.
Connect an option card to the drive.
2
125