YASKAWA GA800 Maintenance & Troubleshooting page 316

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

4.5 Drive Watt Loss
The rated output current
Model
T103
T140
T168
T208
T250
T302
T371
T414
T477
T568
T605
T720
316
Table 4.6 Drive Watt Loss (Normal Duty)
Carrier Frequency
A
kHz
103
2
140
2
168
2
208
2
250
2
296
2
371
2
389
2
453
2
568
2
675
2
720
2
Interior Unit Loss
Cooling Fin Loss
W
223
320
389
434
594
718
694
698
1042
1214
1281
1459
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Total Loss
W
W
725
948
1053
1373
1164
1553
1406
1840
1646
2240
2158
2876
2561
3255
2423
3121
3329
4371
3989
5203
4572
5853
5184
6643

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents