3.10 H: Terminal Functions
Setting Value
Function
4B
During Short Circuit Braking
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
4E
Braking Transistor Fault (rr)
4F
Braking Resistor Overheat
(rH)
60
Internal Cooling Fan Failure
61
Pole Position Detection
Complete
62
Modbus Reg 1 Status
Satisfied
63
Modbus Reg 2 Status
Satisfied
65
Standby Output
66
Comparator1
67
Comparator2
69
External Power 24V Supply
6A
Data Logger Error
90
DWEZ Digital Output 1
91
DWEZ Digital Output 2
92
DWEZ Digital Output 3
93
DWEZ Digital Output 4
A0
DWEZ Extended Digital
Output 1
A1
DWEZ Extended Digital
Output 2
A2
DWEZ Extended Digital
Output 3
A3
DWEZ Extended Digital
Output 4
A4
DWEZ Extended Digital
Output 5
212
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates during Short Circuit Braking.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the fast stop is in operation.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and oH [Heatsink
Overheat] does not clear after the drive decreases the frequency for 10 cycles.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking Transistor Fault]
fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat] fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a cooling fan failure in the drive.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position of the PM motor.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register address set with
H2-07 [Modbus Register 1 Address Select] activates.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register address set with
H2-09 [Modbus Register 2 Address Select] activates.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates after the drive stops operating and after the time set with b8-51 [Standby Mode Wait Time].
ON : The Run command turns on and the magnetic contactor on the input side turns on.
OFF : The Run command turns off and the drive stops operating. Then, the magnetic contactor on the input side turns off after the
time set in b8-51 [Standby Mode Wait Time] elapses.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values of H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator 1 On-Delay Time].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the values of H2-
27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30 [Comparator 2 On-Delay Time].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : The external 24V power supply is supplying power.
OFF : The external 24V power supply is not supplying power.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 1. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 5. Refer to the DriveWorksEZ online manual for more information.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting