YASKAWA GA800 Maintenance & Troubleshooting page 194

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

3.9 F: Options
No.
Name
(Hex.)
F7-15
Communication Speed
Selection
(03F3)
F7-16
Timeout Value
(03F4)
F7-17
EtherNet/IP Speed Scaling
Factor
(03F5)
F7-18
EtherNet/IP Current Scale
Factor
(03F6)
F7-19
EtherNet/IP Torque Scale
Factor
(03F7)
F7-20
EtherNet/IP Power Scaling
Factor
(03F8)
F7-21
EtherNet/IP Voltage Scale
Factor
(03F9)
F7-22
EtherNet/IP Time Scaling
(03FA)
F7-23
Dynamic Out Param 1 for
CommCard
(03FB)
F7-24
Dynamic Out Param 2 for
CommCard
(03FC)
F7-25
Dynamic Out Param 3 for
CommCard
(03FD)
F7-26
Dynamic Out Param 4 for
CommCard
(03FE)
F7-27
Dynamic Out Param 5 for
CommCard
(03FF)
F7-28
Dynamic Out Param 6 for
CommCard
(0370)
F7-29
Dynamic Out Param 7 for
CommCard
(0371)
F7-30
Dynamic Out Param 8 for
CommCard
(0372)
194
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communications speed.
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for a communications timeout.
Note:
Set this parameter to 0.0 to disable the connection timeout function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the scaling factor for the speed monitor in the EtherNet/IP Class ID 2AH Object.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the scaling factor for the output current monitor in the EtherNet/IP Class ID 2AH Object.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the scaling factor for the torque monitor in the EtherNet/IP Class ID 2AH Object.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the scaling factor for the power monitor in the EtherNet/IP Class ID 2AH Object.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the scaling factor for the voltage monitor in the EtherNet/IP Class ID 2AH Object.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
V/f
CL-V/f
OLV
CLV
AOLV
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable
output 1.
V/f
CL-V/f
OLV
CLV
AOLV
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable
output 2.
V/f
CL-V/f
OLV
CLV
AOLV
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable
output 3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a ProfiNet option, set this parameter to set to configurable output
4.
V/f
CL-V/f
OLV
CLV
AOLV
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a PROFINET option, set this parameter to set to configurable
output 5.
V/f
CL-V/f
OLV
CLV
AOLV
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0.
V/f
CL-V/f
OLV
CLV
AOLV
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0.
V/f
CL-V/f
OLV
CLV
AOLV
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Default
(Range)
10
(10, 100 - 102)
0.0 s
(0.0 - 30.0 s)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
0
0
0
0
0
0
0