YASKAWA GA800 Maintenance & Troubleshooting page 213

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Setting Value
Function
A5
DWEZ Extended Digital
Output 6
A6
DWEZ Extended Digital
Output 7
A7
DWEZ Extended Digital
Output 8
100
!During Run
101
!Zero Speed
102
!Speed Agree 1
103
!User-Set Speed Agree 1
104
!Frequency Detection 1
105
!Frequency Detection 2
106
!Drive Ready
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 6. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 7. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output 8. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when you input a Run command and when the drive is outputting voltage.
ON : Drive is stopping
OFF : Drive is running
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is less than E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero
SpeedThreshold].
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting
0
Open Loop V/f Control
1
V/f Control with Encoder
2
Open Loop Vector
3
Closed Loop Vector
4
Advanced OpenLoop Vector Control
5
PM Open Loop Vector Control
6
PM Advanced Open Loop Vector
7
PM Closed Loop Vector Control
8
EZ Open Loop Vector Control
ON : The output frequency is the value of E1-09 or more, or b2-01 or more.
OFF : The output frequency is less than the value of E1-09 or b2-01.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection
Width].
Note:
In CLV, the motor speed is the reference.
ON : The output frequency does not align with the frequency reference although the drive is running.
OFF : The output frequency is in the range of "frequency reference ± L4-02".
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Note:
• The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse
detection level.
• When using Closed Loop Vector Control, this is the value of "Motor Speed ± L4-02."
ON : The output frequency is not in the range of "L4-01 ± L4-02" nor the range of frequency reference ± L4-02.
OFF : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ± L4-02.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level] + L4-02
[Speed Agree Detection Width]. When the terminal activates, it stays activated until the output frequency = L4-01.
Note:
• The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse
detection level.
• In CLV, the motor speed is the reference.
ON : The output frequency is higher than L4-01 + L4-02.
OFF : The output frequency is less than L4-01 or is not more than L4-01 + L4-02.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level]. When the
terminal deactivates, it stays deactivated until the output frequency = L4-01 - L4-02.
ON : The output frequency is less than "L4-01 - L4-02," or it is not more than L4-01.
OFF : The output frequency is more than L4-01.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive is ready and running.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
E1-09
E1-09
b2-01
E1-09
E1-09
E1-09
E1-09
b2-01
E1-09
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
3.10 H: Terminal Functions
Parameter Used as the Reference
3
213