Setting Value
Function
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
16
Motor 2 Selection
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1A
Accel/Decel Time Selection
2
1B
Programming Lockout
1E
Reference Sample Hold
20
External Fault (NO-Always-
Ramp)
21
External Fault (NC-Always-
Ramp)
22
External Fault (NO-@Run-
Ramp)
23
External Fault (NC-@Run-
Ramp)
24
External Fault (NO-Always-
Coast)
25
External Fault (NC-Always-
Coast)
26
External Fault (NO-@Run-
Coast)
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting 10 [Up
Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to operate the motor in the reverse direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a
fault.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is ON while the
drive is operating.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
ON : Selects motor 2
OFF : Selects motor 1
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is ON while the
drive is operating.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable PID control when b5-01 = 1 to 8 [PID Mode Setting = Enabled].
ON : PID control disabled
OFF : PID control enabled
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and H1-xx = 7 [Accel/Decel Time Selection 1] together. Sets the drive to use Acceleration/Deceleration Time 3
[C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to sample the frequency reference at terminals A1, A2, or A3 and hold the frequency reference at that frequency.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-MC will turn
ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates during run, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is stopped.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates during run, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is stopped.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal deactivates, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal activates during run, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is stopped.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
3.10 H: Terminal Functions
3
199