YASKAWA GA800 Maintenance & Troubleshooting page 171

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

No.
Name
(Hex.)
C5-24
Motor 2 ASR Integral Time
2
(0359)
RUN
C5-25
Motor 2 ASR Limit
(035A)
C5-26
Motor 2 ASR Delay Time
(035B)
C5-27
Motor 2 ASR Gain
Switchover Freq
(035C)
C5-28
Motor 2 ASR Integral Limit
(035D)
C5-29
Speed Control Response
(0B18)
Expert
C5-32
Motor 2 Integral Oper at
Acc/Dec
(0361)
C5-37
Motor 2 Inertia
(0278)
Expert
C5-38
Motor 2 Load Inertia Ratio
(0279)
Expert
C5-39
ASR Primary Delay Time
Const 2
(030D)
C5-50
Notch Filter Frequency
(0B14)
Expert
C5-51
Notch Filter Bandwidth
(0B15)
Expert
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ASR integral time for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Set the motor 2 ASR output limit as a percentage of E1-04 [Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor 2 filter time constant of the torque reference output from the speed loop. Usually it is
not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency where the drive will switch between these parameters:
C5-21 and C5-23 [Motor 2 ASR Proportional Gain 1/2]
C5-22 and C5-24 [Motor 2 ASR Integral Time 1/2]
V/f
CL-V/f
OLV
CLV
AOLV
Set the upper limit of the motor 2 ASR integral amount as a percentage of the rated load.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level of speed control responsiveness. Usually it is not necessary to change this setting.
0 : Standard
1 : High Performance 1
V/f
CL-V/f
OLV
CLV
AOLV
Sets ASR integral operation during acceleration and deceleration for motor 2.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor inertia for motor 2.
Note:
The display units for the default setting and setting range are different for different models:
• 0.0001 kgm
2
units (setting range: 0.0001 kgm
• 0.001 kgm
2
units (setting range: 0.001 kgm
T103
• 0.01 kgm
2
units (setting range: 0.01 kgm
to T720
V/f
CL-V/f
OLV
CLV
AOLV
Sets the load inertia ratio for the motor 2 inertia.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the filter time constant used when the torque reference is output from ASR. Usually it is not
necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the machine resonance frequency.
Note:
Set C5-50 = 0 [0 Hz] to disable the notch filter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the notch width of the notch filter.
Note:
Set C5-50 = 0 [Notch Filter Frequency = 0 Hz] to disable the notch filter.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2
to 6.0000 kgm
2
): 2004 to 2021, 4002 to 4012
2
2
to 60.000 kgm
): 2030 to 2211, 4018 to 4103,
2
to 600.00 kgm
2
): 2257 to 2415, 4140 to 4720, T140
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
3.6 C: Tuning
Default
(Range)
Determined by E3-01
(0.000 - 60.000 s)
5.0%
(0.0 - 20.0%)
Determined by E3-01
(0.000 - 0.500 s)
0.0
(0.0 - 400.0)
400%
(0 - 400%)
0
(0, 1)
0
(0, 1)
Determined by o2-04, C6-01
(0.0001 - 600.00 kgm
2
)
1.0
(0.0 - 6000.0)
0.000 s
(0.000 - 0.500 s)
0 Hz
(0, or 2 to 100 Hz)
1.0
(0.5 - 5.0)
3
171