Technical data
Information:
The following figure and table exclusively show the thermal view of the complete system. If additional
space is required for operating or servicing the device, this must be taken into account during instal-
lation.
S1: ≥100 mm
S2: ≥50 mm
S3: ≥100 mm
S4: ≥50 mm
Caution!
The specified spacing for air circulation applies to worst case operation at the maximum specified
ambient temperature. The maximum specified ambient temperature is not permitted to be exceeded!
If the specified spacing for air circulation cannot be maintained, the maximum specified temperatures
of the temperature sensors (see
the user and appropriate measures taken if these values are exceeded.
24
S1
S4
S3
Figure 2: Automation PC 3100 - Spacing for air circulation
"Temperature sensor positions" on page
Automation PC 3100 User's manual V 1.00 Translation of the original documentation
S2
30) must be monitored by