Installing The Automation Pc; Procedure - B&R Automation PC 3100 User Manual

Hide thumbs Also See for Automation PC 3100:
Table of Contents

Advertisement

Commissioning
• Requirements regarding standards and certifications of the device must be observed -
certifications".
• The device is only certified for use in closed rooms.
• The device is not permitted to be exposed to direct sunlight.
• The ventilation holes are not permitted to be covered.
• When installed in a closed housing, there must be sufficient volume for air circulation -
for air
circulation".
Information:
If additional space is required for operating or servicing the device, this must be taken into
account during installation.
• The device must be installed on a flat, clean and burr-free surface.
• It is important to ensure that the wall or control cabinet plate can support four times the total weight of the
device. If necessary, bracing must be attached to reinforce the mounting surface.
Caution!
If the load-bearing capacity of the mounting surface is insufficient, or if the fastening material
is inadequate or incorrect, the device may fall and become damaged.
• The device is not permitted to be placed near other heat sources that could cause overheating.
• When connecting cables (DVI, SDL, USB, etc.), the bend radius must be observed.
• When connecting built-in or connected peripherals, follow the instructions in the peripheral device's docu-
mentation.
Caution!
Built-in or connected peripherals, e.g. a USB drive, are not permitted to introduce any voltage
into the device. Energy regeneration is generally not permitted and can damage the device.
• Observe the notes and regulations regarding the power supply and functional ground.

3.1.2 Installing the Automation PC

The Automation PC 3100 is installed using the mounting holes on the mounting plate. The holes are designed for
M5 screws. The two M5 screws needed for this are not included in delivery.
For the exact position of the mounting holes, see section

3.1.2.1 Procedure

1. Provide the mounting surface with the necessary holes. For the exact position of the mounting holes, see
the drilling templates.
2. Install the B&R industrial PC with M5 screws.
122
Figure 20: Mounting hole
"Drilling template" on page
Automation PC 3100 User's manual V 1.00 Translation of the original documentation
see "Standards and
Ø5.5
Ø11
23.
2.2.2.3 "Spacing

Advertisement

Table of Contents
loading

Table of Contents