5Ac901.I485-00 - B&R Automation PC 3100 User Manual

Hide thumbs Also See for Automation PC 3100:
Table of Contents

Advertisement

Technical data

2.3.5.2 5AC901.I485-00

2.3.5.2.1 General information
Interface option 5AC901.I485-00 is equipped with an RS232/422/485 interface. The operating mode (RS232/
RS422/RS485) is selected automatically depending on the electrical connection.
• 1x RS232/422/485 interface
• Compatible with APC910/PPC900 and APC3100/PPC3100
2.3.5.2.2 Order data
Model number
Short description
Interface options
5AC901.I485-00
Interface card - 1x RS232/422/485 interface - For APC910/
PPC900/APC3100/PPC3100
2.3.5.2.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Model number
General information
B&R ID code
Certifications
CE
UL
HazLoc
DNV GL
GOST-R
Interfaces
COM
Type
Design
UART
Max. baud rate
Terminating resistor
Electrical characteristics
Power consumption
Operating conditions
Pollution degree per EN 61131-2
Environmental conditions
Temperature
Operation
Storage
Transport
72
Table 69: 5AC901.I485-00 - Order data
Class I, Division 2, Groups ABCD, T3C
RS232/422/485, galvanically isolated
Table 70: 5AC901.I485-00 - Technical data
Automation PC 3100 User's manual V 1.00 Translation of the original documentation
Figure
5AC901.I485-00
0xD84A
Yes
cULus E115267
Industrial control equipment
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
1)
Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: A (0.7 g)
EMC: B (Bridge and open deck)
2)
Yes
DSUB, 9-pin, male
16550-compatible, 16 byte FIFO
115 kbit/s
Yes
1 W
Pollution degree 2
0 to 55°C
3)
-20 to 60°C
-20 to 60°C