5Ac901.Bups-01 - B&R Automation PC 3100 User Manual

Hide thumbs Also See for Automation PC 3100:
Table of Contents

Advertisement

2.3.6.5 5AC901.BUPS-01

2.3.6.5.1 General information
• Battery unit for UPS IF option 5AC901.IUPS-01
• Maintenance-free lead acid battery
• 2 Panasonic 12 V 2.2 Ah rechargeable batteries connected in series
• Rated voltage 24 V
• Capacity 2.2 Ah
The battery unit is subject to wear and should be replaced regularly (after the specified service life at the latest).
Warning!
Battery unit 5AC901.BUPS-01 is only permitted to be operated with UPS IF option 5AC901.IUPS-01!
Information:
If the max. specified temperature limits of the battery unit are overshot or undershot, the temperature
alarm of the battery unit is set. Battery backing is no longer provided if the temperature alarm for the
battery unit is active. The battery is also no longer charged since this can result in damage to the
battery. This temperature alarm is defined with a hysteresis of 5°C, i.e. the temperature alarm is only
cleared again if the minimum temperature limit is again overshot by this hysteresis or the maximum
temperature limit is again undershot by this hysteresis. The temperature or temperature alarm of the
battery unit can be read/evaluated using the B&R ADI Library or the B&R implementation guide.
2.3.6.5.2 Order data
Model number
Short description
Uninterruptible power supplies
5AC901.BUPS-01
Battery unit 2.2 Ah - For UPS 5AC901.IUPS-01
Required accessories
Uninterruptible power supplies
5CAUPS.0005-01
UPS cable - 05 m - For 5AC901.IUPS-xx
5CAUPS.0010-01
UPS cable - 1 m - For 5AC901.IUPS-xx
5CAUPS.0013-01
UPS cable - 13 m - For 5AC901.IUPS-xx
5CAUPS.0030-01
UPS cable - 3 m - For 5AC901.IUPS-xx
2.3.6.5.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Model number
General information
Battery
Type
Service life
Design
Temperature sensor
Maintenance interval during storage
Certifications
CE
UL
HazLoc
GOST-R
Charge duration when battery low
Automation PC 3100 User's manual V 1.00 Translation of the original documentation
Table 139: 5AC901.BUPS-01 - Order data
Panasonic 12 V 2.2 Ah; two rechargeable batteries connected in series
Class I, Division 2, Groups ABCD, T3C
Table 140: 5AC901.BUPS-01 - Technical data
Figure
5AC901.BUPS-01
Up to 5 years at 20°C
1)
Maintenance-free lead acid battery
NTC resistance
Charge 1 time every 6 months
Yes
cULus E115267
Industrial control equipment
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
2)
Yes
Typ. 5 hours
Technical data
113

Advertisement

Table of Contents
loading