Parameters/address space
4.1
Parameters
The table below shows the parameters for the DIQ 4+DQ 4x24VDC/0.5A 4xM12 digital
input/digital output module.
Table 4- 1
Parameters
Diagnostics: Missing load voltage 2L+ •
Diagnostics: Short-circuit to ground
Freely assignable channel 0 ... 3
Reaction to CPU/master STOP
Substitute value channel 0 ... 7
Digital input/digital output module DIQ 4+DQ 4x24VDC/0.5A 4xM12 (6ES7143-5AF00-0BA0)
Equipment Manual, 08/2021, A5E36683613-AB
Parameters
Value range
Default
Disable
Disable
•
Enable
Disable
•
Disable
•
Enable
DI
•
DI
•
DQ
Shut down
•
Shut down
•
Keep last value
•
Output substi-
tute value
0
•
0
•
1
4
Scope
Module
Module
(Short-circuit of
encoder supply or
of the output to
ground)
Channel
Module
(digital outputs)
Channel
(digital outputs)
17