Interrupts/diagnostic messages/diagnostics
6.5 Fault types, causes, and corrective measures
Event ID
Diagnostic
message
16x0313
Failure in the
input circuit
16x031C
Input shorted to P F-DI 4/F-DQ 2
16x031E
Read back failure
16x0320
Overload
16x0321
Supply or load
voltage too high
16x0322
Supply or load
voltage too low
Once the fault is eliminated, reintegrate the fail-safe module (return to normal state) from passivation into the safety
1
program.
76
F-DI 4/F-DQ 2
Description
Fail-Safe
module
F-DI 4/F-DQ 2
Internal fault at the
digital inputs
read circuit/test circuit
Input shorted to P
digital inputs
failure
F-DI 4/F-DQ 2
The module has de-
digital outputs
tected a channel prob-
lem where the
expected terminal
voltage(s) are not
reached
F-DI 4/F-DQ 2
Overload condition at
digital outputs
the output driver that
leads to passivation of
the channel
Module
Supply voltage (1L+) or
load voltage (2L+)
maximum exceeded
Module
Supply voltage (1L+) or
load voltage (2L+)
minimum exceeded
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Possible causes
Corrective measures
The module digital
inputs detect a
failure during bit
pattern testing of
inputs
EMI or module
hardware fault
External wiring or
sensor shorts input
signal to L+
Input configured
for internal sensor
supply with short-
circuit detection
enabled, but wired
to external L+
Input defective
"Maximum read-
back time" or "Max-
imum readback
time switch on
test" configured
value is too small
Output switch
failure
Overload at output
Eliminate overload
Supply or load voltage
Adjust supply or load
is set too high
voltage
Supply or load voltage
Adjust supply or load
is set too low
voltage
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
1
If intermittent, it is
probably due to in-
terference; elimi-
nate the
interference
If persistent, or
repeats after ef-
forts to eliminate
interference, re-
place the fail-safe
module
Check/correct ex-
ternal short-circuit
Make wiring and
configuration agree
Replace the fail-
safe module
Increase readback
time
Replace the fail-
safe module if out-
put does not re-
spond