Technical specifications
Article number
Output voltage
•
for signal "1", min.
Output current
•
for signal "1" rated value
•
for signal "0" residual current, max.
Switching frequency
•
with resistive load, max.
•
with inductive load, max.
•
on lamp load, max.
Total current of the outputs
•
Current per group, max.
Cable length
•
unshielded, max.
Encoder
Connectable encoders
•
2-wire sensor
–
permissible quiescent current (2-wire
sensor), max.
Interrupts/diagnostics/status information
Substitute values connectable
Alarms
•
Diagnostic alarm
Diagnoses
•
Short-circuit
Diagnostics indication LED
•
Channel status display
•
for module diagnostics
•
For load voltage monitoring
Potential separation
between the load voltages
Potential separation channels
•
between the channels, in groups of
•
between the channels and backplane bus
•
between the channels and the power sup-
ply of the electronics
Isolation
Isolation tested with
Degree and class of protection
IP degree of protection
26
6ES7143-5BF00-0BA0
L+ (-0.8 V)
0.5 A
0.5 mA
100 Hz
0.5 Hz
1 Hz
2 A
30 m
Yes
1.5 mA
Yes; channel by channel, parameterizable
Yes; Parameterizable
Yes; Outputs to M; encoder supply to M; module
by module
Yes; green LED
Yes; green/red LED
Yes; green LED
Yes
4; DIQ channels are isolated from DQ channels
Yes
No; DIQ channels are non-isolated and DQ chan-
nels are isolated from supply voltage 1L+
707 V DC (type test)
IP65/67
Digital input/digital output module DIQ 4+DQ 4x24VDC/0.5A 8xM8 (6ES7143-5BF00-0BA0)
Equipment Manual, 08/2021, A5E32349882-AD