Article number
Load resistance range
•
•
Output voltage
•
Output current
•
•
•
Switching frequency
•
•
•
Total current of the outputs
•
Cable length
•
IO-Link
IO-Link protocol 1.1
Transmission rate
Cycle time, min.
Size of process data, input per module
Size of process data, output per module
Supported IO-Link profiles
Cable length unshielded, max.
Connection of IO-Link devices
•
Interrupts/diagnostics/status information
Substitute values connectable
Alarms
•
Diagnoses
•
Diagnostics indication LED
•
•
•
IO-Link digital output module DQ 8x24VDC/2A 8xM12 (6ES7142-5AF00-0BL0)
Equipment Manual, 08/2021, A5E47926730-AB
lower limit
upper limit
for signal "1", min.
for signal "1" rated value
for signal "1" permissible range, max.
for signal "0" residual current, max.
with resistive load, max.
with inductive load, max.
on lamp load, max.
Current per module, max.
unshielded, max.
Port type A
Diagnostic alarm
Short-circuit
Channel status display
for module diagnostics
For load voltage monitoring
Technical specifications
6ES7142-5AF00-0BL0
12 Ω
4 kΩ
L+ (-0.8 V)
2 A (45 °C); 1 A (55 °C)
2 A; with inductive load to IEC 60947-5-1, DC-13 /
AC-15
0.5 mA
100 Hz
0.1 Hz; 0.25 Hz at 25 °C
1 Hz
8 A
30 m
Yes
38.4 kBd (COM2)
2.1 ms
0 byte
1 byte
common profile
20 m
Yes
Yes; channel by channel, parameterizable
Yes; Parameterizable
Yes; Outputs to ground; module by module
Yes; green LED
Yes; green/red LED
Yes; green LED
21