Siemens SIMATIC ET 200AL System Manual page 108

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Technical specifications
10.3 Transport and storage conditions
10.3
Transport and storage conditions
Transport and storage conditions
The modules of the ET 200AL distributed I/O system exceed the specifications regarding
transport and storage conditions pursuant to IEC 61131-2. The following table shows the
conditions that apply to modules transported or stored in their original packaging.
Table 10- 8
Type of condition
Free fall
Temperature
Temperature variation
Barometric pressure
Relative humidity
10.4
Mechanical and climatic ambient conditions
Operating conditions
The ET 200AL distributed I/O system is suitable for use in weather-proof, fixed locations.
• The conditions of use exceed the requirements pursuant to IEC 61131-2
– Class OTH2
You can find the values for the operating conditions in the technical specifications of the
manuals or on the Internet (https://support.industry.siemens.com/cs/de/en/view/109742718).
Tests of mechanical ambient conditions
The following table shows the type and scope of the tests on mechanical ambient conditions.
Table 10- 9
Condition tested
Vibrations
Shock
106
Transport and storage conditions
Tests of mechanical ambient conditions
Test standard
Vibration test accord-
ing to IEC 60068-2-6.
Shock, tested accord-
ing to IEC 60068-2-27
Permissible range
≤0.3 m
-40 °C to +70 °C
20 K/h
from 1140 hPa to 660 hPa
(corresponds to a height of-1000 to 3500 m)
from 5 to 95%
Values
Type of oscillation: Frequency sweeps with a rate of
change of 1 octave/minute.
5 Hz to 9.1 Hz, constant amplitude 15 mm
9.1 Hz to 150 Hz, constant acceleration 10g
Duration of oscillation: 10 frequency sweeps per axis at
each of three vertically aligned axes
Type of shock: Half-sine
Shock intensity: 30g peak value, 18 ms duration
Direction of shock: 3 shocks each in ± direction in each
of the 3 axes vertical to one another
System Manual, 08/2021, A5E31861578-AJ