Pulse-shaped disturbance variables
The following table shows the electromagnetic compatibility of the ET 200AL IO-Link I/O
modules with respect to pulse-shaped disturbance variables.
Table 9- 1
Pulse-shaped disturbance variable
Electrostatic discharge according to
IEC 61000-4-2.
Burst pulses (rapid transient disturbance
values) according to IEC 61000-4-4.
Sinusoidal disturbance variables
The tables below show the electromagnetic compatibility of the ET 200AL IO-Link I/O
modules with respect to sinusoidal disturbance variables.
Table 9- 2
80 ... 1000 MHz
1.4 ... 6 GHz
80% AM (1 kHz)
Table 9- 3
0.15 ... 80 MHz
10 V
80% AM (1 kHz)
150 Ω source impedance
56
Pulse-shaped disturbance variables
RF radiation
RF radiation according to IEC 61000-4-3
Electromagnetic RF field, amplitude modulated
RF coupling (signal and supply cables)
RF coupling according to IEC 61000-4-6.
unmodulated
rms
Tested with
Air discharge: ±8 kV
Contact discharge: ±4 kV
±2 kV (power supply cable)
±1 kV (signal line <30 m)
10 V/m
3 V/m
System Manual, 08/2021, A5E48755395-AB
Conforms to degree of
severity
3
2
3
3
Conforms to degree of
severity
3
2
Conforms to degree of
severity
3
IO-Link I/O modules