Parameters/address space
4.1
Measurement types and measuring ranges
The table below indicates which measuring range is configurable.
Table 4- 1
Measurement type
Deactivated
Voltage
Thermocouple
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
Equipment Manual, 08/2021, A5E48753535-AB
Measurement type and measuring ranges
Measuring range
+/- 80 mV
Resistance
(2-wire connection)
Resistance
(3-wire connection)
Resistance
(4-wire connection)
Thermal resistor
(2-wire connection)
Thermal resistor
(3-wire connection)
Thermal resistor
(4-wire connection)
Type: B, C, E, J, K, L, N,
R, S, T, U
Temperature coeffi-
cient
150 Ω
300 Ω
Pt 100 climatic
range
Pt 100 standard
range
Pt 1000 climatic
range
Pt 1000 standard
range
Ni 100 climatic
range
Ni 100 standard
range
Ni 1000 climatic
range
Ni 1000 standard
range
Resolution
Max. 16-bit
Max. 15-bit
Max. 16-bit incl. sign
Pt 0.003851
(EN 60751)
Pt 0.003916
Pt 0.003902
Pt 0.00392
Pt 0.00385
Max. 16-bit incl. sign
Ni 0.00618
Ni 0.00672
Max. 16-bit incl. sign