Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
Documentation guide The documentation for the SIMATIC ET 200AL distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The System Manual and Getting Started describe in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200AL distributed I/O system.
Page 7
You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en). "mySupport" - Documentation In the Documentation area in "mySupport" you can combine entire manuals or only parts of these to your own manual.
Page 8
With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet (http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool). SIMATIC Automation Tool You can use the SIMATIC Automation Tool to perform commissioning and maintenance activities simultaneously on different SIMATIC S7 stations as a bulk operation, independently of the TIA Portal.
Page 9
Documentation guide PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the system network during commissioning. PRONETA features two core functions: ● The topology overview independently scans the PROFINET network and all connected components. ● The IO check is a fast test of the wiring and the module configuration of a system.
Product overview Properties Article number 6ES7147-5JD00-0BA0 View of the module Figure 2-1 View of the CM 4xIO-Link 4xM12 communication module Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0) Manual, 10/2017, A5E32352322-AE...
Page 11
Product overview 2.1 Properties Properties The module has the following technical properties: ● IO-Link Master according to IO-Link specification V1.1 ● 4 ports, type class B ● 4 M12 connectors ● SIO mode (standard IO mode) ● Supported data transmission rates: –...
Page 12
● M8 sealing cap ● M12 sealing cap See also You can find more information on accessories in the Accessories/spare parts section of the ET 200AL distributed I/O system (http://support.automation.siemens.com/WW/view/en/89254965) system manual. Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0) Manual, 10/2017, A5E32352322-AE...
Product overview 2.2 Operator controls and display elements Operator controls and display elements The following figure shows the operator controls and display elements of the CM 4xIO-Link 4xM12 communication module. ① DIAG: LED display for mode and diagnostic status ② C1 to C4: LED displays for port status ③...
24 V DC technology. Reference For more information on the IO-Link system, please see the IO-Link system (http://support.automation.siemens.com/WW/view/en/65949252) function manual. Reset communication module to factory settings Effects of resetting to the factory settings Use the "Reset to factory settings" function to restore the parameter assignments of your CM 4xIO-Link 4xM12 communication module made with S7-PCT to the factory state.
Wiring Terminal and block diagram The following figure shows an example of the pin assignment for Port Class A (Type A) and Port Class B (Type b). ① SIO input Loop-through of the ET-Connection ② SIO output Supply voltage 1L+ (non-switched) ③...
Wiring 3.2 Pin assignment Pin assignment Note Color coding The sockets for ET-Connection and the power supply of the modules are color-coded. These colors correspond to the colors of the offered cables. Pin assignment of the IO-Link sockets Note Port Class B The pin assignment of the IO-Link interface corresponds to the IO-Link specification as per Port Class B.
Page 17
Wiring 3.2 Pin assignment NOTICE 24 V encoder supply 1U For the supply of devices, only use the 24 V 1U encoder supply provided by the communication device. Pin assignment of the sockets for ET-Connection The table below shows the pin assignments of the 2 sockets for the connection of ET-Connection.
Page 18
Wiring 3.2 Pin assignment Pin assignment of the socket for loop-through of the supply voltage The table below shows the pin assignment of the socket for loop-through of the supply voltage. Table 3- 4 Pin assignment of the supply voltage socket Assignment Assignment of the wire color Front view of the...
Parameters/address space Parameters Parameters The following table shows the general parameters for the communication module CM 4xIO-Link 4xM12. Table 4- 1 General parameters Parameters Value range Default Scope Diagnostics Diagnostics: No supply voltage 2L+ Disable Module Disable • Enable • Diagnostics port 1 Disable Channel...
Page 20
Parameters/address space 4.1 Parameters The following table shows the port parameters for the communication module CM 4xIO-Link 4xM12 with firmware version V1.1. Table 4- 2 Port parameters Parameters Range of values Default Port configuration Operating mode IO-Link autostart IO-Link autostart •...
Parameters/address space 4.2 Explanation of the parameters Explanation of the parameters Diagnostics: No supply voltage 2L+ Enabling of the diagnostics for no or insufficient supply voltage 2L+. Diagnostics port This parameter enables the diagnostics for the selected port. The diagnostics possible depends on the IO-Link device in use. Additional information about the diagnostic interrupts can be found in the description of the utilized IO-Link device.
Page 22
● Type-compatible (V1.1) with Backup&Restore ● Type-compatible (V1.1) with Restore You can find the Vendor ID and Device ID on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109748852). The port is operating as a standard digital input. The port is operating as a standard digital output.
Page 23
Parameters/address space 4.2 Explanation of the parameters Port configuration You can use a CM 4xIO-Link 4xM12 communication module as of firmware version V1.1 to commission the IO-Link ports of the IO-Link master or the connected IO-Link devices in two different ways: ●...
Page 24
The following figure show the structure of the PQI byte. You enable a parameter by setting the corresponding bit to "1". Figure 4-1 Structure of the PQI byte Reference For more information, please refer to the IO-Link system (http://support.automation.siemens.com/WW/view/en/65949252) function manual. Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0) Manual, 10/2017, A5E32352322-AE...
Diagnostics alarms Status and error displays LED displays The following figure shows the LED display of the CM 4xIO-Link 4xM12 communication module. ① Diagnostics (DIAG) (green/red) ② Port status / IO-Link status (Cn) (green) ③ Load voltage 2L+ (PWR) (green) ④...
Page 26
Diagnostics alarms 5.1 Status and error displays DIAG LED Table 5- 1 Error display of the DIAG LED DIAG LED Meaning No supply voltage 1L+ Module parameters not assigned • (after switching on the supply voltage 1L+) Flashes Loading firmware •...
Diagnostics alarms 5.2 Diagnostics alarms LEDs Qn Valid for IO-Link port in SIO mode. Table 5- 4 Status displays of the Q1, Q2, Q3, and Q4 LEDs Q1, Q2, Q3, and Q4 LEDs Meaning Process signal = 0 in SIO mode, deactivated or in IO-Link mode Process signal = 1 in SIO mode Diagnostics alarms For each diagnostic event, a diagnostics alarm is issued and the DIAG LED flashes red on...
Page 28
Diagnostics alarms 5.2 Diagnostics alarms Diagnostics Error Meaning (IO-Link error code) IO-Link IO-Link alarm code master device Parameter Incorrect device (1802 • assignment error Vendor ID and Device ID not defined (1817 • Process data length of the IO-Link device exceeded (1818 •...
Technical specifications Technical specifications of the CM 4xIO-Link 4xM12 communication module Article number 6ES7147-5JD00-0BA0 General information Product type designation CM 4 x IO-Link HW functional status Firmware version V1.1.x Product function Yes; I&M0 to I&M3 I&M data • Engineering with STEP 7 V15 or higher STEP 7 TIA Portal configurable/integrated •...
Page 30
Technical specifications Article number 6ES7147-5JD00-0BA0 Encoder supply Number of outputs 24 V encoder supply Yes; per module, electronic Short-circuit protection • 1.4 A; Total current of all ports Output current, max. • Power loss Power loss, typ. 2.6 W IO-Link Number of ports of which simultaneously controllable •...
Page 31
Technical specifications Article number 6ES7147-5JD00-0BA0 Diagnostics indication LED Yes; Green LED Channel status display • Yes; Green/red LED for module diagnostics • Yes; Green LED For load voltage monitoring • Potential separation between the load voltages Potential separation channels between the channels •...
(https://support.industry.siemens.com/cs/ww/en/view/65949252) function manual. Reference You will find additional information on replacing modules in the system manual ET 200AL distributed I/O system (http://support.automation.siemens.com/WW/view/en/89254965) in the "Module" section. You will find additional information on replacing IO-Link masters in the S7-PCT online help.
Additional information You can find additional information on working with PROFIenergy in the "PROFIenergy" section of the manual IM 157-1 PN interface module (http://support.automation.siemens.com/WW/view/en/89254863) and the "Saving energy with PROFIenergy" section of function manual PROFINET with STEP 7 V13 (http://support.automation.siemens.com/WW/view/en/49948856).
PROFIenergy 8.2 DI operating mode DI operating mode Display If no external supply voltage is connected, switching off supply voltages 1U and 2U also leads to switching off the associated channel status LED Qn. Response to error detection All channels that are in pause mode on "PE_MODE_PROCEED" report their diagnostic status as in productive mode.
PROFIenergy 8.3 DQ operating mode DQ operating mode Display The channel status LEDs Qn show the output value. Response to error detection All channels that are in pause mode on "PE_MODE_PROCEED" report their diagnostic status as in productive mode. The following applies for all channels which switch to a different pause mode: ●...
PROFIenergy 8.4 IO-Link operating mode IO-Link operating mode Display Switching off the supply voltage 1U also switches off the associated port status LED Cn. Response to error detection All channels which are set to "PE_MODE_PROCEED" and "PE_MODE_LAST_VALUE" in pause mode report errors as in productive operation. The following conditions apply to all channels (ports) which switch to a different pause mode ("PE_MODE_SHUTDOWN"...
Page 37
PROFIenergy 8.4 IO-Link operating mode Note Supply voltages 1U and 2U Supply voltages 1U and 2U can only be switched off separately for each module. If all channels require switching off in the pause, the supply voltages are switched off. Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0) Manual, 10/2017, A5E32352322-AE...
Dimension drawing The following figure shows the dimension drawing of the CM 4xIO-Link 4xM12 communication module in front and side view. Figure A-1 Dimension drawing Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0) Manual, 10/2017, A5E32352322-AE...