Configuration control (option handling)
7.3 Creating the control data record
Note
The data in the feedback data record is always mapped for all modules. In a Shared Device
configuration, it is therefore irrelevant which IO controller the respective modules are
assigned to.
As long as no control data record was sent, a one-to-one module assignment is assumed for
the compilation of data record 197 (station master → station option).
Error messages
In the case of an error when reading the feedback data record, the RDREC instruction returns
the following error messages via the STATUS block parameter:
Table 7- 4
Error code
80B1
80B5
80B8
74
Error messages
Meaning
Invalid length; the length information in data record 197 is not correct.
H
Configuration control not configured
H
Parameter error
H
The following events cause a parameter error:
Incorrect block ID in the header (not equal to 197)
Invalid version identifier in the header
A reserved bit was set
Multiple slots in the station master are assigned to the same slot in the station
option
Distributed I/O system
System Manual, 08/2021, A5E31861578-AJ