Table B- 15
Thermocouple type T
Type T
Values
in °C
Dec.
Hex.
> 540.0
32767
7FFF
540.0
5400
1518
:
:
:
400.1
4001
0FA1
400.0
4000
0FA0
:
:
:
-270.0
-2700
F574
< -270.0
-32768
8000
Table B- 16
Thermocouple type U
Type U
Values
in °C
Dec.
Hex.
> 850.0
32767
7FFF
850.0
8500
2134
:
:
:
600.1
6001
1771
600.0
6000
1770
:
:
:
-200.0
-2000
F830
< -200.0
-32768
8000
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
Equipment Manual, 08/2021, A5E48753535-AB
Type T
Values
in °F
Dec.
Hex.
> 1004.0
32767
7FFF
1004.0
10040
2738
:
:
:
752.1
7521
1D61
752.0
7520
1D60
:
:
:
-454.0
-4540
EE44
< -454.0
-32768
8000
Type U
Values
in °F
Dec.
Hex.
> 1562.0
32767
7FFF
1562.0
15620
2738.0
:
:
:
1112.1
11121
2B71
1112.0
11120
2B70
:
:
:
-328.0
-3280
F330
< -328.0
-32768
8000
Representation of analog values
B.4 Representation of analog values for thermocouples
Type T
Values
in K
Dec.
> 813.2
32767
813.2
8132
:
:
673.3
6733
673.2
6732
:
:
3.2
32
< 3.2
-32768
Type U
Values
in K
Dec.
> 1123.2
32767
1123.2
11232
:
:
873.3
8733
873.2
8732
:
:
73.2
732
< 73.2
-32768
Range
Hex.
7FFF
Overflow
1FC4
Overrange
:
1AAD
1AAC
Nominal range
:
0020
8000
Underflow
Range
Hex.
7FFF
Overflow
2BE0
Overrange
:
221D
221C
Nominal range
:
02DC
8000
Underflow