Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Table 5- 6
Diagnostics
alarm
Short-circuit
High limit violat-
ed
Low limit violat-
ed
Error
Parameter error
Hardware inter-
rupt lost
Table 5- 7
Diagnostics
alarm
Wire break
High limit violat-
ed
Parameter error
Hardware inter-
rupt lost
Note
Measurement type resistor (3-wire terminal)
A wire break of the M+ cable is not detected with measurement type resistor (3-wire
terminal). An incorrect measuring value is output in this case.
36
Diagnostics alarms - for the measuring range: 0 V to 10 V and 4-DMU 0 mA to 20 mA
Error code
Meaning
1
Short-circuit encoder supply to
H
ground
7
Value is above overrange.
H
8
Value is below underrange.
H
9
Value is significantly above or
H
below underrange/overrange.
10
Module parameter assignment is
H
faulty
16
At least one hardware interrupt
H
could not be signaled because
too many hardware interrupts are
pending.
Diagnostics alarms - for the measuring range: 150 Ω and 300 Ω
Error code
Meaning
6
Impedance of encoder circuit too
H
high
Wire break between the module
and sensor
Channel not connected (open)
7
Value is above overrange.
H
10
Module parameter assignment is
H
faulty
16
At least one hardware interrupt
H
could not be signaled because
too many hardware interrupts are
pending.
Remedy
Correct interplay between mod-
ule and encoder
Correct interplay between mod-
ule and sensor
Correct interplay between mod-
ule and sensor
Correct interplay between mod-
ule and sensor
Correct the parameter assign-
ment
Correct the program or the pro-
cess
Remedy
Use a different encoder type or
modify the wiring, for example,
using cables with larger cross-
section
Connect the cable
Correct interplay between mod-
ule and sensor
Correct the parameter assign-
ment
Correct the program or the pro-
cess
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Equipment Manual, 08/2021, A5E32350124-AG
Deactivate diagnostics
Connect the channel
Deactivate channel