The following table is used to explain the channel error entries.
Channel number
Channel properties
Channel error type
IM 157-1 DP (6ES7157-1AA00-0AB0)
Equipment Manual, 08/2021, A5E32100641-AE
Interrupts, error messages, diagnostics and system alarms
Description
0 ... 63: Channel number for channel error
0x8000: Entire submodule
Bits 0 to 7
00
: Free data type
H
01
: bit
H
02
: 2 bit
H
03
: 4 bit
H
04
: byte
H
05
: word
H
06
: double word
H
07
to FF
: Reserved
H
H
Bit 8
0: Channel
1: Channel group
Bit 9, 10
00
: Diagnostics
H
01
: Maintenance demanded
H
02
: Maintenance required
H
03
: Reserved
H
Bit 11, 12
00
: Channel error-free
H
01
: Incoming diagnostics
H
02
: Outgoing diagnostics
H
03
: Outgoing diagnostics, but other diagnostics are also
H
pending on this channel
Bits 13 to 15 00
: Reserved
H
01
: Input channel
H
02
: Output channel
H
03
: Input/output channel
H
Explanations are available in the device manuals, in the section "Diagnostic
alarms".
5.2 Interrupts