Siemens SIMATIC ET 200AL System Manual page 409

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

4.3
Address space
The figure below shows the assignment of the address space for the digital input module
DI 16x24VDC 8xM12 with value status (Quality Information, QI).
The address space for the value status is allocated by the module, if the value status is
configured using the PROFINET interface module.
Figure 4-1
Configuration options of the DI 16x24VDC 8xM12 digital input module
You have the following configuration options:
• Configuration 1: without value status
• Configuration 2: with value status
Evaluating the value status
An additional two bytes are occupied in the input address space if you enable the value status
for the digital input module. Bits 0 to 7 in these bytes are assigned to a channel and return
information about the validity of the digital input value.
Bit = 1: No error on channel.
Bit = 0: Error on channel.
DI 16x24VDC 8xM12 (6ES7141-5AH00-0BA0)
Equipment Manual, 08/2021, A5E36681813-AB
Address space
Parameters/address space
4.3 Address space
17