Ssr Parameters; Ssm Parameters - Danfoss Vacon OPTEA Operating Manual

Hide thumbs Also See for Vacon OPTEA:
Table of Contents

Advertisement

VACON® NXP Advanced Safety Options
Operating Guide

8.10 SSR Parameters

Table 78: SSR Parameters
Parameter
Selection
Acknowledg-
Manual
ment Mode
Automatic
(SSR)
SSR Ramp
None
Monitoring
Ramp 1
Ramp 2
SSR t1
0...3 000 000
SSR td1
20...65535
SSR td2
0...65535
SSR Max Limit
0...65535
SSR Min Limit
0...65535

8.11 SSM Parameters

Table 79: SSM Parameters
Parameter
Selection
Acknowledg-
Manual
ment Mode
Automatic
(SSM)
Always Active
Active
Inactive
SSM td2
0...65535
SSM Max
0...65535
Limit
SSM Min Lim-
0...65535
it
Danfoss A/S © 2021.06
Unit
Description
Use this parameter to select if manual (external) acknowledgment is necessary to deacti-
vate the safety function after the request ends. If the selection is automatic, the function
is deactivated after the request ends.
Use this parameter to select the monitored ramp.
ms
Use this parameter to set the time after which the SSR function must be reached.
ms
Use this parameter to set the time after the activation of the function during which the
ramp monitoring must start (when ramp monitoring used).
ms
Use this parameter to set the time during which the speed must stay below the SSR limit
speed before the function becomes reached.
rpm
Use this parameter to set the monitored maximum speed limit that is used when the SSR
function is active. Setting the value to 0 disables the monitoring of the maximum limit.
rpm
Use this parameter to set the monitored minimum speed limit that is used when the SSR
function is active. Setting the value to 0 disables the monitoring of the minimum limit.
Unit
Description
Use this parameter to select if manual (external) acknowledgment is necessary to deactivate
the safety function after the request ends. If the selection is automatic, the function is deac-
tivated after the request ends.
NOTE! This parameter is valid only when the SSM function is not set to always active.
Use this parameter to set the SSM function to be always active. A checkbox selection.
NOTE! When the SSM function is set to always active, it is not possible to assign an input for
it or request it over a safe fieldbus.
ms
Use this parameter to set the time during which the speed must stay within the monitored
limits before the function becomes reached.
rpm
Use this parameter to set the monitored maximum speed limit that is used when the SSM
function is active.
NOTE! Setting the value to 0 disables the monitoring of the maximum limit.
rpm
Use this parameter to set the monitored minimum speed limit that is used when the SSM
function is active.
NOTE! Setting the value to 0 disables the monitoring of the minimum limit.