Ramp Parameters - Danfoss Vacon OPTEA Operating Manual

Hide thumbs Also See for Vacon OPTEA:
Table of Contents

Advertisement

VACON® NXP Advanced Safety Options
Operating Guide
Parameter
Selection
Sin/Cos with termination
Sin/Cos with termination
and proximity sensor
TTL with termination and
proximity sensor
TTL with termination and es-
timated speed
Proximity sensor and estima-
ted speed
Encoder Power
5
Supply
12
15
24
Encoder Reference
Reference Signal Used
Signal
No Reference Signal
Encoder Number
1...65535
of Pulses
Proximity Sensor
1...100
Number of Pulses
Proximity Sensor
1...99
Duty Cycle
Gear Ratio Divider
1...65535
Gear Ratio Multi-
1...65535
plier
Allowed Deviation
0...1000
of Speed Sources
Speed Deviation
0...5000
Timer

8.1.4 Ramp Parameters

Table 66: Ramp Parameters
Parameter
Selection
Ramp1 Speed
0...65535
Ramp1 Acc Time
0...3 000 000
Min
Ramp1 Acc Time
0...3 000 000
Max
126 | Danfoss A/S © 2021.06
Unit
Description
V
Use this parameter to select the power supply voltage for the en-
coder.
Use this parameter to set the reference signal on or off.
Use this parameter to select the number of pulses per revolution of
the encoder.
Use this parameter to select the number of pulses per revolution of
the proximity sensor.
%
Use this parameter to select the duty cycle of the proximity sensor,
that is, the active/inactive signal ratio. Other ratios than 50% (1:1)
will decrease the supported maximum frequency of the proximity
sensor signals. This parameter is used to determine that the fre-
quency of the input signal will not exceed the detection capability
and cause pulses to be lost.
Use this parameter together with Gear Ratio Multiplier to set the ra-
tio between the speed measured by an external sensor and the esti-
mated speed.
Use this parameter together with Gear Ratio Divider to set the ratio
between the speed measured by an external sensor and the estima-
ted speed.
rpm
Use this parameter to set the allowed deviation between the two
speed sources.
ms
Use this parameter to set the time that the value of Allowed Devia-
tion of Speed Sources can be exceeded.
Unit
Description
rpm
Use this parameter to set the nominal speed that is used to define the ramp 1.
ms
Use this parameter to set the minimum time for the speed to accelerate from zero to
Ramp1 Speed.
ms
Use this parameter to set the maximum time for the speed to accelerate from zero to
Ramp1 Speed.
Parameter List
AQ319736045637en-000101 / DPD01798

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vacon optblVacon optbmVacon optbn

Table of Contents