Safe Fieldbus Parameters; Profisafe Parameters; Sto And Sbc Parameters - Danfoss Vacon OPTEA Operating Manual

Hide thumbs Also See for Vacon OPTEA:
Table of Contents

Advertisement

VACON® NXP Advanced Safety Options
Operating Guide
Parameter

8.3 Safe Fieldbus Parameters

8.3.1 PROFIsafe Parameters

Table 69: PROFIsafe Parameters
Parameter
Selection
Fieldbus type
PROFIsafe
F Source Address
1...65534
F Destination Ad-
1...65534
dress
F WD Time
20...65535
Safety Telegram
3031 58000

8.4 STO and SBC Parameters

Table 70: STO and SBC Parameters
Parameter
Selection
Acknowledgment
Manual Auto-
Mode (STO)
matic
Table 71: SBC Parameters
Parame-
Selection
Unit
ter
SBC Ena-
bled
SBC Order
SBC first
STO first
SBC t1
0...99.9
s
SBC
0...999
rpm
Speed
Danfoss A/S © 2021.06
Selection
Warning in any safety function
Limit violation error in any safety function
Unit
Description
Use this parameter to select the safe fieldbus.
Use this parameter to set a codename between sender and recipient. The source ad-
dress must be unique within a subnet.
Use this parameter to set a codename between sender and recipient. The destina-
tion address must be unique within a subnet.
ms
Use this parameter to set the PROFIsafe watchdog time in F-Device. See
FIsafe Watchdog
Use this parameter to select the safety telegram. See
FIdrive on
PROFIsafe.
Unit
Description
Use this parameter to select if manual (external) acknowledgment is necessary to
deactivate the safety function after the request ends. If the selection is automatic,
the function is deactivated after the request ends.
Description
Use this parameter to enable the SBC safety function.
Use this parameter to select which safety function activates first when the conditions for activa-
tion apply. The second safety function activates after the time set with SBC t1. See the tables in
6.2.2.3 The STO Function Used with the SBC
Use this parameter to set the delay between the activation of the STO and the SBC functions. See
the tables in
6.2.2.3 The STO Function Used with the SBC
This parameter is only valid for the activation. The deactivation of the STO and the SBC functions
always occurs simultaneously.
Use this parameter to set the speed at which the first function, STO or SBC, activates. SBC Speed
is used with SS1 and SQS-SS1 safety functions.
When you use the value 0 for SBC Speed, and a non-zero value for Zero Speed, Zero Speed is
used instead as the condition for the first safety function to activate. See the tables in
STO Function Used with the SBC
Unit
Description
Time.
Function.
Function.
Function.
AQ319736045637en-000101 / DPD01798 | 129
Parameter List
7.1.5.2 PRO-
7.1.6.4 Data Mapping for PRO-
6.2.2.3 The