VACON® NXP Advanced Safety Options
Operating Guide
12.2.13 Fault Code 20 - Safety System, S12 - General, Fault Number Any
Cause
•
Internal fault in the option board.
Troubleshooting
•
Reboot the AC drive.
•
If the fault reoccurs, contact the nearest distributor.
12.2.14 Fault Code 20 - Safety System, S17 - Comm. Error, Fault Number Any
Cause
•
Incompatible control and option board firmware.
Troubleshooting
•
Reboot the AC drive.
•
Update the control and/or option board firmware.
•
If the fault reoccurs, contact the nearest distributor.
12.2.15 Fault Code 20 - Safety System, S18 - External I/O, Fault Number 1
Cause
•
Channels of a two channel input are in different state.
Troubleshooting
•
Check the cabling.
•
Check the connected systems.
•
Reboot the AC drive.
12.2.16 Fault Code 20 - Safety System, S18 - External I/O, Fault Number 2
Cause
•
One channel caused a short request (input inactive) for a safety function before returning to not requested state (input active).
The other channel did not change.
Troubleshooting
•
Check the cabling.
•
Check the connected systems.
•
Deactivate both channels before activating them again, then acknowledge the safety function.
12.2.17 Fault Code 20 - Safety System, S32 - SafeF Common, Fault Number 3
Cause
•
The reset signal has not been accepted because a safe stopping function executed as a violation response has not been
reached.
Troubleshooting
•
Allow the safe stopping function to finish its execution.
12.2.18 Fault Code 20 - Safety System, S32 - SafeF Common, Fault Number 4
Cause
•
The reset signal cannot be accepted as the speed is above a monitoring limit at requested monitoring function.
Troubleshooting
•
Check the requested safety functions.
•
Check the motor speed and the speed sensors.