12.2.58 Fault Code 20 - Safety System, S65 - PROFIsafe, Fault Number 5
Cause
The PROFIsafe telegram is commanding the AC drive to a failsafe state.
Troubleshooting
Acknowledge the situation in PLC.
12.2.59 Fault Code 20 - Safety System, S65 - PROFIsafe, Fault Number Other
Cause
Fault in the communication between the option board and the external safe fieldbus master.
Interference.
Troubleshooting
Check the fieldbus parameters in option boards and PLC.
Check the cabling.
12.2.60 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 64
Cause
The F Destination Address does not match.
Troubleshooting
Check the F-parameters in the option board and the safety PLC.
12.2.61 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 65
Cause
The F Destination Address is outside the valid range.
Troubleshooting
Check the F-parameters in the option board and the safety PLC.
12.2.62 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 66
Cause
The F Source Address does not match.
Troubleshooting
Check the F-parameters in the option board and the safety PLC.
12.2.63 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 67
Cause
The Watchdog time F WD Time is 0 or invalid.
Troubleshooting
Check the F-parameters in the option board and the safety PLC.
12.2.64 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 69
Cause
The length of the F parameter CRC does not match.
Troubleshooting
Check the F-parameters in the option board and the safety PLC.
160 | Danfoss A/S © 2021.06
Fault Tracing
AQ319736045637en-000101 / DPD01798