VACON® NXP Advanced Safety Options
Operating Guide
should be set based on the use of the light curtain. If you want to prevent automatic deactivation of the SLS function after the light
curtain detects no objects, use manual acknowledgment. The drive reset is used to deactivate the STO function and to reset the
faults.
The SQS-SS1 function is used as a violation response of the SLS function and assigned to a digital input for requests. The SQS-SS1
function is used in time monitoring mode with a 5.0 s delay for the STO activation. The SQS-SS1 function can operate in the auto-
matic or the manual acknowledgment mode with the drive acknowledgment enabled.
The SQS-SS1 request is assigned to Digital Input 1 of the Advanced safety option board. The SLS 1 control is assigned to Digital
Input 2.
The drive application is used to limit the speed to the desired value. A Sin/Cos encoder is used to measure the speed of the motor
shaft.
Table 108: Configuration in OPTBN: Used Safety Functions: SLS, SQS
SLS parameters
Acknowledgment Mode (SLS)
SLS Ramp Monitoring
SLS t1
SLS td1
SLS td2
SLS td3
SLS 1 Limit
SLS 2 Limit
SLS 3 Limit
Table 109: Input/Output Parameters
Input/output parameters
Digital Input 1
Digital Input 2
Table 110: General Parameters
General parameters
Drive Reset
Drive Acknowledgment
Table 111: Speed Measurement Configuration
Speed measurement configuration
Encoder Type
Encoder power supply
Encoder reference signal
178 | Danfoss A/S © 2021.06
Configuration Examples
Value
Manual, Automatic
None
5.0 s
20 ms
100 ms
250 rpm
0 rpm
0 rpm
Value
SS1
SLS 1
Value
Enabled
Enabled 2)
Disabled 1)
Value
Sin/Cos
15 V
No reference signal
AQ319736045637en-000101 / DPD01798