Programming

7.3 Quick Menu

The Quick Menu gives easy access to the most frequently
used parameters.
1.
To enter the Quick Menu, press [Menu] key until
indicator in display is placed above Quick Menu.
2.
Use [
] [
] to select either QM1 or QM2, then
press [OK].
3.
Use [
] [
] to browse through the parameters in
the Quick Menu.
4.
Press [OK] to select a parameter.
5.
Use [
] [
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
To exit, press either [Back] twice to enter Status,
or press [Menu] once to enter Main Menu.
Illustration 7.9 Indicating Quick Menu Mode
VLT Micro Drive Design Guide

7.4 Quick Menu Parameters

7.4.1 Quick Menu Parameters - Basic
Below are descriptions of all parameters found in the Quick
Menu.
* = Factory setting.
1-20 Motor Power [kW]/[HP] (P
Option:
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.0 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
NOTE
Changing this parameter affects parameter 1-22 to 1-25,
1-30, 1-33 and 1-35.
1-22 Motor Voltage (U
Range:
230/400 V
1-23 Motor Frequency (f
Range:
50 Hz
®
MG02K102 - VLT
is a registered Danfoss trademark
Settings QM1
m.n
Function:
Enter motor power from nameplate
data.
Two sizes down, one size up from
nominal VLT rating.
0.09 kW/0.12 HP
0.12 kW/0.16 HP
0.18kW/0.25 HP
0.25 kW/0.33 HP
0.37kW/0.50 HP
0.55 kW/0.75 HP
0.75 kW/1.00 HP
1.10 kW/1.50 HP
1.50 kW/2.00 HP
)
m.n
Function:
[50 - 999 V] Enter motor voltage from nameplate
data.
)
m.n
Function:
[20-400 Hz] Enter motor frequency from nameplate
*
data.
)
65
7
7