10 Operation and Maintenance

10.1 Gathering Diagnostic Data
When additional information on the option board is necessary, you can use these sources of information.
You can monitor certain values using the monitoring or datalogger tools of the AC drive and the PC software.
The drive info and the used parameter file can be downloaded from the AC drive. Newer versions of the tools of the AC drive
can download all relevant information when downloading service info. Old tools download only the drive info, and you must
download the parameter file manually with the VACON
The option board saves the states of the relevant internal values when changes to these values occur. This activity log can be
downloaded with the VACON
You can use the control panel or the PC tools of the AC drive to browse parameter and monitoring values.
When you contact the manufacturer for support, provide at least the service info of the AC drive including the parameter file. If the
support request is related to the behavior of the AC drive or the option board in certain situations, also provide the datalogger, the
monitoring log, or the option board activity log.
The hardware revision is printed on the main board of the option board.
The firmware version of the option board can be found in 2 ways.
Finding the firmware version of the option board:
Use the VACON
Safe tool. Connect to the drive in question. Select the symbol "?" and then select "About". The tool shows the
®
firmware version of the option board and the version of the PC tool.
Use the control panel of the AC drive.
See chapter
3.8.3 Option Board Menu on the Control
Table below lists the Advanced safety option specific values that should be considered for logging when submitting support re-
quest for Danfoss support. The needed signals depend on the situation that is being monitored.
Table 83: Internal Variables of the Drive for Monitoring and Logging
Variable
Source/
type
SafetyEncoder-
Firmware
Speed
Firmware
SafetyFunctionRe-
questWordDIN
SafetyFunctionRe-
questWordPLC
SafetyFunction-
Firmware
StatusWord
Danfoss A/S © 2021.06
Safe tool.
®
Safe tool.
®
Panel.
Description
The speed measured by Advanced safety option from encoder and proximity sensor.
Unit: rpm
When using multiple sensors (e.g. two proximity sensors) this value displays the average of the
speed measured from the two sensors.
Displays the state of the request for safety functions from digital input (DIN) or over PROFIsafe
(PLC).
0 = The safety function is not requested.
1 = The safety function is requested.
B0 = STO
B1 = SS1
B2 = SS2
B3 = SQS
B4 = SSR
B5 = SLS1
B6 = SLS2
B7 = SLS3
B10 = SSM
B11 = SMS
Displays the state of the safety functions. Corresponds to the Active signal of the safety func-
tion.
0 = The safety function is not active.
1 = The safety function is active.
B0 = STO
Operation and Maintenance
AQ319736045637en-000101 / DPD01798 | 139