NOTE! The faults that are shown and their type (Fault or
Warning) depend on the settings of the AC drive.
NOTE! F47 SafetyReached, subcode: SS2 (3), indicates that
the SS2 safety function is Reached and that the SOS safety
function is active.
6
Make the motor rotate so that the rotation exceeds the SOS
position deviation limit.
7
Make sure that the position deviation at which the SOS
safety function detects the rotation violation is valid for the
process.
The expected violations:
Warning: F48 SafetyViolat, Safety function: SOS, Fault
number: 1.
8
Make sure that the drive is in NOT READY state.
9
Deactivate the SS2 function.
Send a reset signal to the option board.
NOTE! When a safety function is deactivated, and there is a
valid RUN request in the AC drive, the AC drive can start
running unexpectedly.
10
Make sure that the drive is in READY state.
The SS2 tests have been executed, possible deviations documented and
testing approved.
Notes:
3.7.4

SQS

3.7.4.1 SQS-STO
The SQS function as a violation response is tested during the testing of a safety function that uses the SQS
function as its violation response.
The SQS-STO function from an external source: the test instructions are similar to that of STO + SBC test
instructions in 3.7.1 STO + SBC.
Step
STO-1
Make sure that the drive is in READY state.
Make sure that no safety functions are requested.
Instructions
VACON
Comments
13