VACON® NXP Advanced Safety Options
Operating Guide
12.2.65 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 70
Cause
•
The F parameter version is incorrect.
Troubleshooting
•
Check the F-parameters in the option board and the safety PLC.
12.2.66 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 71
Cause
•
The F parameter CRC does not match.
Troubleshooting
•
Check the F-parameters in the option board and the safety PLC.
12.2.67 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number 75
Cause
•
The device specific parameter CRC (iParameter CRC) does not match.
Troubleshooting
•
Check the F-parameters in the option board and the safety PLC.
12.2.68 Fault Code 20 - Safety System, S67 - F-Parameter, Fault Number Other
Cause
•
Fault in the communication between the option board and the external safe fieldbus master.
•
Interference.
Troubleshooting
•
Check the fieldbus parameters in option boards and PLC.
•
Check the cabling.
12.2.69 Fault Code 20 - Safety System, S68 - PROFIdrive, Fault Number 1
Cause
•
Invalid or unsupported data in the control word.
•
A wrong telegram used.
Troubleshooting
•
Check the programming of the safety PLC.
•
Check the parameters.
12.2.70 Fault Code 20 - Safety System, S68 - PROFIdrive, Fault Number Other
Cause
•
Fault in the communication between the option board and the external safe fieldbus master.
•
Interference.
Troubleshooting
•
Check the fieldbus parameters in option boards and PLC.
•
Check the cabling.
Danfoss A/S © 2021.06
Fault Tracing
AQ319736045637en-000101 / DPD01798 | 161