Estimated Speed Parameters; Safe I/O Parameters; Digital Input/Output Parameters - Danfoss Vacon OPTEA Operating Manual

Hide thumbs Also See for Vacon OPTEA:
Table of Contents

Advertisement

VACON® NXP Advanced Safety Options
Operating Guide
Parameter
Selection
Ramp1 Dec Time
0...3 000 000
Min
Ramp1 Dec Time
0...3 000 000
Max
Ramp2 Speed
0...65535
Ramp2 Acc Time
0...3 000 000
Min
Ramp2 Acc Time
0...3 000 000
Max
Ramp2 Dec Time
0...3 000 000
Min
Ramp2 Dec Time
0...3 000 000
Max

8.1.5 Estimated Speed Parameters

Table 67: Estimated Speed Parameters
Parameter
Selection
Coast Stop Time
0...10800

8.2 Safe I/O Parameters

8.2.1 Digital Input/Output Parameters

Table 68: Digital Input/Output Parameters
Parameter
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Output 1
Danfoss A/S © 2021.06
Unit
Description
ms
Use this parameter to set the minimum time for the speed to decelerate from Ramp1
Speed to zero.
ms
Use this parameter to set the maximum time for the speed to decelerate from
Ramp1 Speed to zero.
rpm
Use this parameter to set the nominal speed that is used to define the ramp 2.
ms
Use this parameter to set the minimum time for the speed to accelerate from zero to
Ramp2 Speed.
ms
Use this parameter to set the maximum time for the speed to accelerate from zero to
Ramp2 Speed.
ms
Use this parameter to set the minimum time for the speed to decelerate from Ramp2
Speed to zero.
ms
Use this parameter to set the maximum time for the speed to decelerate from
Ramp2 Speed to zero.
Unit
Description
s
Use this parameter to set the time that it is estimated for the motor to coast to stop after
the drive stops operating. The set value must be maximum 3 hours.
Selection
STO(+SBC)
SS1
SS2 + SOS
SQS
SLS input 1
SLS input 2
SSR
SSM
SMS
SS1 Ramp
SS2 Ramp
Acknowledgment
Reset
Acknowledgment + Reset
SSM
SBC
Group 1
Group 2
Group 3
Unit
Description
Use this parameter to select the func-
tion for a digital input.
The configuration of an input is disa-
bled if a proximity sensor is used for
that input. Digital Input 1: one proxim-
ity sensor, and Digital Input 1 & 2: two
proximity sensors.
Use this parameter to select the func-
tion for the digital output.
AQ319736045637en-000101 / DPD01798 | 127