VACON® NXP Advanced Safety Options
Operating Guide
VOLTAGE WITHSTAND TESTS
Doing voltage withstand tests can damage the drive.
-
Do not do voltage withstand tests on the AC drive. The manufacturer has already done the tests.
SHOCK HAZARD FROM PE CONDUCTOR
The drive can cause a DC current in the PE conductor. Failure to use a residual current-operated protective (RCD) device Type B or
a residual current-operated monitoring (RCM) device can lead to the RCD not providing the intended protection and therefore
can result in death or serious injury.
-
Use a type B RCD or RCM device on the mains side of the drive.
Danfoss A/S © 2021.06
N O T I C E
W A R N I N G
AQ319736045637en-000101 / DPD01798 | 23
Safety
Need help?
Do you have a question about the Vacon OPTEA and is the answer not in the manual?