Sdl4 Receiver (5Dlsd4.1001-00) - B&R Automation Panel 1000 User Manual

Table of Contents

Advertisement

4.1.5.3 SDL4 receiver (5DLSD4.1001-00)

4.1.5.3.1 Overview
The interfaces available on the device or module are numbered for the purpose of clear differentiation.
This numbering used by the operating system may deviate, however.
The receiver interfaces are located on the back of the device.
No.
Interface name
1
USB1
2
USB2
3
SDL4 In
4.1.5.3.2 +24 VDC power supply
Danger!
The device is only permitted to be supplied with a SELV/PELV power supply or with safety extra-low
voltage (SELV) per EN 60950.
The necessary 3-pin connector is not included in delivery; for suitable accessories, see 0TB103.9x.
The device is protected against overload and reverse polarity by a soldered fuse (15 A, fast-acting). If the fuse
is defective (e.g. due to overload), the device must be sent to B&R for repairs. If the polarity is reversed, it is not
necessary to replace the fuse.
Pin
1
2
3
Reverse polarity protection
3-pin
Male
Electrical properties
Nominal voltage
Nominal current
Overvoltage category per EN 61131-2
Galvanic isolation
Uninterruptible power supply
1)
EN 60950 requirements must be observed.
Automation Panel 1000 user's manual V2.00
(3)
(2)
(1)
Figure 10: Overview of interfaces - SDL3 receiver link module
Chapter
USB interfaces
USB interfaces
SDL4 In interface
Description
-
Functional ground
+
(6)
(5)
(4)
No.
Interface name
4
SDL4 In LEDs
5
Power 24 VDC
6
Grounding
24 VDC ±25%, SELV
1)
Max. 3 A
II
Yes
No
Technical data
Chapter
SDL4 In interface
+24 VDC power supply
Grounding
Figure
1 2 3
49

Hide quick links:

Advertisement

Table of Contents
loading