B&R Automation Panel 1000 User Manual page 184

Table of Contents

Advertisement

International and national certifications
B&R device (connected device)
V
oc
I
sc
C
a
L
a
If the electrical parameters of the cable are unknown, the following values can be used:
Where C
= 196.85 pF/m (60 pF/ft) if unknown
Cable
Where L
= 0.656 μH/m (0.20 μH/ft) if unknown
Cable
Wiring must be carried out in accordance with national regulations and the requirements of the authorities.
The B&R device must be installed in a suitable protective housing. For installations in Class I, Division 2 hazardous
locations, the housing must be capable of withstanding one or more Division 2 wiring methods.
Warning!
• Replacing components may impair the suitability of the Division 2 hazardous location (classi-
fied) under certain circumstances.
• As long as the area is knowingly at risk of explosion, the device is not permitted to be switched
on or off.
• The nonincendive device with field wiring is not permitted to be connected via a parallel con-
nection. This is valid unless the device has received express permission for this.
The B&R device is suitable for use in Class I, Division 2, Groups A, B, C and D areas. It also provides nonincendive
field wiring for devices in Class I, Division 2, Groups A, B, C and D.
184
Table 81: Connected, nonincendive device with field wiring
-
Connected, nonincendive device with field wiring (mouse, keyboard)
V
max
I
max
C
+ C
i
Cable
L
+ L
i
Cable
Automation Panel 1000 user's manual V2.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents