4.1.3.3 Spacing for air circulation

To ensure sufficient air circulation, a specified clearance must be provided above, below, to the side and behind
the device. For the minimum specified clearance, see the following diagrams. This is valid for all variants.
Information:
The following figure and table exclusively show the thermal view of the complete system. If additional
space is required for operating or servicing the device, this must be taken into account during instal-
lation.
S1: ≥10 mm
S2: ≥ 50 mm
S3: ≥80 mm
S4: ≥ 50 mm
Information:
A minimum distance of 30 mm at all points is required to perform the installation with retaining clips.
Caution!
The specified spacing for air circulation is based on worst-case operation at the maximum specified
ambient temperature. The maximum specified ambient temperature is not permitted to be exceeded!
If the specified spacing for air circulation cannot be maintained, the maximum specified temperatures
of the temperature sensors (see
the user and appropriate measures taken if these values are exceeded.
Automation Panel 1000 user's manual V2.00
Rear view
Figure 5: Automation Panel 1000 - Spacing for air circulation
"Temperature sensor positions" on page
Technical data
Side view
36) must be monitored by
29