11.5

JOG operation

The frequency and acceleration/deceleration time for JOG operation can be set.
JOG operation can be used for conveyor positioning, test operation, etc.
Pr.
Name
15
Jog frequency
D200
16
Jog acceleration/
F002
deceleration time
These parameters can be selected from among simple mode parameters when the LCD operation panel (FR-LU08) or the
parameter unit (FR-PU07) is connected to the inverter.
*1
60 Hz is initially set in Pr.20 in Group 1, and 50 Hz in Group 2. (Refer to
 JOG operation by inputting signals (JOG signal and JOG2 signal)
• Operation can be started and stopped by the start signals (STF and STR signals) when the Jog operation selection (JOG)
signal or Jog operation selection 2 (JOG2) signal is ON. (For the operation method, refer to
• The JOG signal can be input only via a control terminal. For the JOG signal, set "5" to any parameter from Pr.178 to Pr.184
(Input terminal function selection)to assign the function to a control terminal.
• The JOG2 signal can be input via a control terminal or via communication. For the JOG2 signal, set "30" to any parameter
from Pr.178 to Pr.189 (Input terminal function selection) to assign the function to a control terminal.
• Use the JOG acceleration/deceleration time function (Pr.16) to set the acceleration/deceleration time for JOG operation.
Output frequency(Hz)
Pr.20
Pr.15
Forward
rotation
setting range
Pr.16
JOG/JOG2 signal
Forward rotation STF
ON
Reverse rotation STR
 JOG operation using the operation panel
• When the operation panel is in the JOG operation mode, the motor jogs only while a key for start command is pressed.
(For the operation method, refer to
NOTE
• The reference frequency during acceleration/deceleration depends on the Pr.29 Acceleration/deceleration pattern
selection setting. (Refer to
• The Pr.15 setting should be equal to or higher than the Pr.13 Starting frequency setting.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
• During JOG operation, the second acceleration/deceleration function using the RT signal is disabled. (Other second functions
are enabled (refer to
• When Pr.79 Operation mode selection = "4", JOG operation is started by one push of the RUN key on the operation panel
and stopped by the STOP/RESET key.
• This function is invalid when Pr.79 = "3".
Parameters referred to
Pr.13 Starting
frequencypage 244
Initial
Setting range
value
5 Hz
0 to 590 Hz
0.5 s
0 to 3600 s
Time
Reverse
rotation
ON
ON
page
50.)
page
238.)
page
374).)
Description
Set the frequency for JOG operation.
Set the motor acceleration/deceleration time during JOG operation.
The acceleration/deceleration time is a period of time that the
inverter takes to increase/decrease the output frequency to the
frequency set in Pr.20 Acceleration/deceleration reference
*1
frequency
.
The acceleration/deceleration times cannot be set separately.
page
54).
11. (D) Operation Command and Frequency Command
page
49.)
11.5 JOG operation
11
12
13
14
15
16
17
18
19
20
271