Setting Multiple Parameters By Batch - Mitsubishi Electric 800 Series Instruction Manual (Function

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

9.13

Setting multiple parameters by batch

The setting of particular parameters is changed by batch, such as communication parameters for connection with the Mitsubishi
Electric human machine interface (GOT), the parameters for the rated frequency (50/60 Hz) setting, or the parameters for
acceleration/deceleration time increment.
Multiple parameters are changed automatically. Users do not have to consider each parameter number (automatic parameter
setting).
Pr.
Name
999
Automatic parameter
E431
setting
*1
The read value is always "9999".
 Automatic parameter setting (Pr.999)
• Select which parameters to automatically set from the following table, and set them in Pr.999. Multiple parameter settings
are changed automatically. Refer to
Pr.999
setting
Automatically sets the communication parameters for the GOT
10
connection with a PU connector ("Controller Type" in GOT:
FREQROL 500/700/800, SENSORLESS SERVO)
Automatically sets the communication parameters for the GOT
12
connection with a PU connector ("Controller Type" in GOT:
FREQROL 800 (Automatic Negotiation))
50 Hz rated
20
frequency
60 Hz rated
21
frequency
NOTE
• If the automatic setting is performed with Pr.999 or the automatic parameter setting mode, the settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the parameters will not cause any problem.
• "AUTO" is displayed on the operation panel also when the user group function is used (Pr.160 = "1"). However, if Pr.999 is
not registered in the group, the automatic setting cannot be performed (write error (Er1) occurs).
 GOT initial setting (PU connector) (Pr.999 = "10, 12") (for standard model)
Pr.
79
Operation mode selection
118
PU communication speed
119
PU communication stop bit length / data length 1
120
PU communication parity check
121
PU communication retry count
122
PU communication check time interval
123
PU communication waiting time setting
124
PU communication CR/LF selection
340
Communication startup mode selection
414
PLC function operation selection
549
Protocol selection
*1
The setting is changed when Pr.414 = "0" (initial setting).
216
9. (E) Environment Setting Parameters
9.13 Setting multiple parameters by batch
Setting
Initial value
range
10
12
*1
9999
20
21
9999
page 216
for the list of parameters that are changed automatically.
Description
Sets the related parameters of the rated
frequency according to the power supply
frequency
Name
GOT initial setting (PU connector)
GOT initial setting (PU connector)
50 Hz rated frequency
60 Hz rated frequency
No action
Operation in the automatic parameter setting mode
"AUTO"→"GOT"→Write "1".
"AUTO"→"GOT"→Write "2".
"AUTO"→"F50"→Write "1".
Initial value
Pr.999 = "10"
0
1
192
192
10
2
1
1
9999
9999
9999
9999
0 ms
1
1
0
0
0
0
0
Description
"Controller Type" in GOT: FREQROL
500/700/800, SENSORLESS SERVO
"Controller Type" in GOT: FREQROL
800 (Automatic Negotiation)
Pr.999 = "12"
Refer to page
1
250
1152
0
1
Instruction Manual
9999
(Communication)
9999
0 ms
1
0
260
*1
457
2
Instruction Manual
0
(Communication)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800 seriesFr-e800Fr-e820-0008Fr-e840-0016Fr-e860-0017Fr-e820s-0008 ... Show all

Table of Contents