Item
Shape of
terminal block
Contact input
Analog input
Control circuit
Relay output
terminal
Open collector
output
Pulse output
Analog output
Safety input/
output
Ethernet
Communication
RS-485
USB
Surrounding air temperature
Storage temperature
Plug-in option
Installation size
Panel through attachment
Machine speed display
Built-in potentiometer switching
Control mode selection
MRS input selection
Offline auto tuning
Applicable motor
Increment/range of acceleration/
deceleration time
 Installation precautions
• Removal procedure of the front cover is different. (Refer to the Instruction Manual (Connection).)
• Plug-in options of the FR-E700 series are not compatible.
 Wiring instructions
• When the FR-E700 standard control circuit terminal model is replaced, the terminal block type is changed from the screw
type to the spring clamp type. Use of blade terminals is recommended.
• To use the PU connector, note that wiring methods are different. (Refer to the Instruction Manual (Connection).)
FR-E800
Spring clamp type
Standard model: 7
Ethernet model: 2
Safety communication model: 0
2
1
Standard model: 2
Ethernet model and safety communication model: 0
1 (FM type only)
1 (AM type only)
S1, S2, PC, SO, SOC
2 ports (Ethernet model and safety communication
model)
CC-Link IE TSN, CC-Link IE Field Network Basic,
EtherNet/IP, PROFINET, MODBUS/TCP, and
BACnet/IP
1 port (standard model)
Mitsubishi inverter protocol, MODBUS RTU
Mini B connector: USB bus power available
(Maximum SCCR: 500 mA)
200/400 V class: -20°C to +60°C (Derate the rated
current when using the inverter in a temperature of
50°C or higher.)
575 V class: -10°C to +60°C (Derate the rated
current when using the inverter in a temperature of
50°C or higher.)
-40°C to +70°C
Dedicated plug-in options (not interchangeable)
Compatible (Use the installation interchange attachment for replacement of the FR-E720-175(3.7K)
and FR-E740-016(0.4K) to 040(1.5K).)
Not compatible
The rotation speed is displayed when Pr.53 = "1".
The machine speed is displayed when Pr.53 = "4".
Use Pr.37 and Pr.505 to set the reference for
machine speed.
Pr.146 unavailable (PA02 not supported)
V/F control when "40" is set in Pr.800.
Use Pr.17 to change the input specifications of the
MRS and X10 signals.
Set Pr.96 = "11" to enable offline auto tuning for V/
F control (frequency search for the automatic restart
after instantaneous power failure).
Offline auto tuning is enabled regardless of the
Pr.71 setting.
Set Pr.71 to a value whose last digit is 3 to change
the setting range of the motor constant.
Set "10" for the constant-torque motor.
The setting range cannot be changed from "0 to
3600 s" even when the increment is 0.01 s (Pr.21 =
"1").
19.1 For customers replacing the conventional model with this inverter
FR-E700
Standard control circuit terminal model: screw
type
Safety stop function model: Spring clamp type
Standard control circuit terminal model: 7
Safety stop function model: 6
2
1
2
1 (FR-E700)
1 (FR-E700-NA/EC/CHT)
S1, S2, PC (safety stop function model only)
1 port (FR-E700-NE only)
CC-Link IE Field Network Basic and MODBUS/
TCP
1 port
Mitsubishi inverter protocol, MODBUS RTU
Mini B connector: USB bus power unavailable
-10°C to +50°C
-20°C to +65°C
The machine speed is displayed when Pr.37 ≠
"0".
Pr.146 available
V/F control when "9999" is set in Pr.80 or Pr.81.
Use Pr.17 to change the input specification of
the MRS signal.
Set Pr.96 = "21" to enable offline auto tuning for
V/F control (frequency search for the automatic
restart after instantaneous power failure).
Set Pr.71 to a value whose last digit is 3 to
enable offline auto tuning.
Set Pr.71 to a value whose last digit is 4 to read
offline auto tuning data and change the setting.
Set "1" for the constant-torque motor.
The setting range can be changed to "0 to 360
s" when the increment is 0.01 s (Pr.21 = "1").
11
12
13
14
15
16
17
18
19
20