10.3

Remote setting function

Even if the operation panel is located away from the enclosure, contact signals can be used to perform continuous variable-
speed operation, without using analog signals.
Pr.
Name
59
Remote function
F101
selection
 Remote setting function
• When Pr.59 ≠ "0" (remote setting enabled), the functions of the signals are as shown in the following table.
Signal name
STF/STR
RH
RM
RL
Terminal 2 (analog signal)
Inverter
Forward
rotation
STF
Acceleration
RH
Deceleration
RM
Clear
RL
SD
Connection
diagram for remote setting
 Main speed
• The main speed used in the remote setting corresponds with each of the following operation modes.
PU operation mode / NET operation mode
External operation mode / PU/External combined operation mode 2 (Pr.79 = "4")
PU/External combined operation mode 1 (Pr.79 = "3")
240
10. (F) Settings for Acceleration/Deceleration
10.3 Remote setting function
Initial
Setting
value
range
0
1
2
3
0
11
12
13
Function
Forward/Reverse
Acceleration
Deceleration
Clear
Main speed
Set frequency
10
2
Terminal 2
5
(main speed)
RH (Acceleration)
RM (Deceleration)
RL (Clear)
STF (Forward)
Operation mode
RH, RM, RL signal
Frequency setting
function
Multi-speed setting
Remote setting
Enabled
Remote setting
Disabled
Disabled
(Turning OFF the STF/STR
Remote setting
signal clears the remotely-
set frequency.)
Remote setting
Enabled
Remote setting
Disabled
Disabled
(Turning OFF the STF/STR
Remote setting
signal clears the remotely-
set frequency.)
The inverter accelerates the motor in the forward or reverse direction up to
the main speed or to the frequency stored by the remote setting function.
The set frequency increases according to the Pr.44 setting.
The set frequency decreases according to the Pr.45 setting.
The set frequency is cleared and the main speed is applied.
The setting of the main speed is used as a base. The main speed is
increased by the RH signal and decreased by the RM signal.
Increased
(Hz)
according to the
Pr.44 setting
ON
ON
Description
Deceleration to the
storage
main speed or lower
Not available
Available
Description
Decreased according to
the Pr.45 setting
Cleared by RL
ON
ON
Main speed
Digital setting
Analog input
Analog input via terminal 4 (AU signal ON)
Time